Free building report

823 N Western Ave

Winter habitability score Multiple habitability signals in public records

Download a PDF of this report

Renter reviews

Firsthand and anonymous. Renter opinions are separate from the city records below.

No renter reviews here yet. If you’ve lived at 823 N Western Ave, yours could be the first.

A Chicago three-flat

Do you live here?

One tap helps other renters. The full building record stays right below.

Sure, I’ll share
How’s it been living here? Required

Tap a star — 1 is rough, 5 is great.

Add more detail (optional — heat, pests, repairs, noise, management)

Tap 1 to 5 for any you want. 1 is rough, 5 is great. Skip the rest.

Heat Warm enough when it counts?
Pests Have pests been a problem?
Maintenance responsiveness When something broke, how fast did it get fixed?
Noise How noisy was it, day to day?
Management How they treated you and answered you
Would you rent here again?

Your own experience only — no fake or paid reviews. Shown anonymously after you confirm and a person approves it. Review policy · Terms

47Open City violation records
0Open heat-related City records
0311 rodent (24 mo)
1311 building (24 mo)

What rat complaints mean →

All open City violation records (47)

No open City violation records dated in the last 24 months (since November 2024). The newest open one is from August 20, 2021. All 47 are collapsed below — still open, still counted.

Show 47 older open City violation records (before November 2024)
  • Open

    EL1886 — Violation

    PROVIDE ANY REQUIRED ROUGH INSPECTIONS FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES, WIRE, DEVICES AND EQUIPMENT FULL GUT REHAB OF MAIN BUILDING AND NEW SERVICE FEEDERS/SERVICE MODIFIED MISCELLANEOUS MODIFICATIONS NO PERMITS INSUFFICIENT PERMITS PREVIOUS PERMITS NO EVIDENCE OF INSPECTIONS (14A-5-505.2)

  • Open

    EL1816 — ADD RECEPTACLES

    ADD RECEPTACLES AT CAR WASH OFFICE AND WHERE REQUIRED TO ELIMINATE EXTENSION CORD USAGE

  • Open

    EL1875 — INSTALL GFCI'S

    INSTALL GFCI PROTECTION EXTERIOR AND WET LOCATIONS

  • Open

    EL1818 — DEFECTIVE OUTLETS

    REPLACE DEFECTIVE SWITCHES AND RECEPTACLES AND INSTALL APPROVED COVERS WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1819 — DEFECTIVE FIXTURES

    BROKEN OPEN LIGHT SOUTH INTERIOR CAR WASH REPAIR/REPLACE LIGHT FIXTURES WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1884 — SEE INSPECTOR COMMENTS

    ALL LIGHT FIXTURES, BOXES, FITTINGS, RACEWAYS, EQUIPMENT IN CARWASH MUST BE SUITABLE FOR WET CORROSIVE LOCATION AND IDENTIFIED FOR USE (14E-1-110.3) DANGEROUS AND HAZARDOUS

  • Open

    EL1885 — Violation

    PROVIDE PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT, BOXES WIRE, DEVICES AND EQUIPMENT FULL GUT REHAB OF MAIN BUILDING AND NEW SERVICE FEEDERS/SERVICE MODIFIED MISCELLANEOUS MODIFICATIONS NO PERMITS INSUFFICIENT PERMITS PREVIOUS PERMITS NO EVIDENCE OF INSPECTIONS (14A-4-404.6)

  • Open

    CN031013 — FIRE EXTNGSHR REQ, RESDNTL

    MISSING EXTINGUISHER AT THE FUEL PUMPS 14X-5-504

  • Open

    CN194019 — REPAIR OR REPLACE

    AISLE RESTRICTED AT REAR OF PROPERTY DUNKIN DONUT AREAS BY SHELVING AND STORE STOCK 14B 10-1018.1

  • Open

    CN067014 — REPAIR ROOF

    ROOF AREAS WITHIN CAR WASH AREA WHERE PLUMBING STACK PROTRUDES THROUGH ROOF MISSING SECTION WITH ROTTED MATERIAL FOR ROOF SYSTEM REPAIRS REQUIRED 14X-303.1.1

  • Open

    CN197089 — CARB MONOX DETECT IN ASSEMBLY

    MISSING CARBON MONOXIDE DETECTORS WITHIN INTERIOR OF PROPERTY AND CAR WASH AREAS 14X5-504.9

  • Open

    PL237004 — INDIRECT CONN.FOR WATER SUPPLY

    SOAP DISPENSER WATER SUPPLY PIPING AT 3 COMPARTMENT SINK AND MOP SINK ARE DIRECTLY CONNECTED WITHOUT ANY MEANS OF CROSS CONNECTION PROTECTION EXPOSING PREMISES TO DANGEROUS AND HAZARDOUS CROSS CONNECTION

  • Open

    PL232011 — OBTAIN PERMIT FOR PLUMBING

    OBTAIN PERMIT BEFORE CONSTRUCTING ALTERING OR USING PLUMBING SYSTEM

  • Open

    PL239010 — ENGAG LIC & BOND PLMBNG CNTRC

    ENGAGE LICENSED AND BONDED CONTRACTOR TO INSTALL PLUMBING

  • Open

    EL1801 — DEFECTIVE SERVICE

    OVERHEAD SERVICE CABLES APPEAR DETERIORATED AT SERVICE HEAD OVERHEAD SERVICE SPLICE COVERS DAMAGED OPEN ENSURE SERVICE IN APPROVED CONDITION DANGEROUS AND HAZARDOUS

  • Open

    EL1806 — PROPER SIZE GRD ELECTRODE COND

    NO VISIBLE WATER GROUND SUPPLEMENT GROUND NOT CONNECTED TO ELECTRODE ENSURE SERVICE GROUNDED IN APPROVAL MANNER DANGEROUS AND HAZARDOUS

  • Open

    EL1809 — WORKING SPACE

    CLUTTER, PRODUCTIONS IN FRONT OF OFFICE ELECTRICAL PANELS AND SERVICE EQUIPMENT DANGEROUS AND HAZARDOUS

  • Open

    EL1836 — PANEL SCHEDULES

    MISSING PANEL SCHEDULES

  • Open

    EL1829 — EXPOSED WIRING

    OPEN WIRING OPEN AIR SPLICES AT OFFICE PANEL TROUGH AREA OPEN WIRING AT EAST EXTERIOR LOT LIGHTS POLE OPEN WIRE ON UPPER PART OF SIGN WEST LOT REMOVE OPEN WIRING WHERE REQUIRED THROUGHOUT DANGEROUS AND HAZARDOUS

  • Open

    EL1823 — INSTALL COVERS

    MISSING HAND HOLE COVER AT SOUTH WEST LOT LIGHT POLE MISSING THROUGH COVER AT OFFICE ELECTRICAL OPEN BOX BEHIND ICE CREAM CASE AT FRONT WINDOW CLOSE OPEN BOXES WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1819 — DEFECTIVE FIXTURES

    UNAPPROVED EXTERIOR BOX COVER AT FRONT EXTERIOR ICE MACHINE INSTALL APPROVED COVERS WHERE REQUIRED

  • Open

    EL1866 — UNAPPROVED CORDS

    DAMAGED CORD AT FRONT WINDOW ICE CREAM CASE EXTENSION CORD THROUGH CEILING AT REAR OFFICE CEILING REMOVE UNAPPROVED CORDS WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1816 — ADD RECEPTACLES

    ADD RECEPTACLES TO ABATE EXTENSION CORD USAGE AT FRONT WINDOW AREA REAR OFFICE AREA CEILING AND WHERE REQUIRED D

  • Open

    EL1817 — CONTINUITY OF RACEWAYS

    LOOSE FITTING AT LIGHT POLE BASE AT EAST EXTERIOR LOT ENSURE GROUND CONTINUITY WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1875 — INSTALL GFCI'S

    INSTALL GFCI PROTECTION EXTERIOR, BATH, SINKS, WET LOCATIONS

  • Open

    EL1827 — RESTORE EXIT AND EM

    EXISTING EMERGENCY LIGHTING AND EXIT SIGNS NOT OPERABLE DANGEROUS AND HAZARDOUS

  • Open

    EL1884 — SEE INSPECTOR COMMENTS

    LIGHT FIXTURES, BOXES, FITTINGS, RACEWAYS AT WALK IN COOLER MUST BE SUITABLE FOR WET LOCATION AND IDENTIFIED FOR USE (14E-1-110.3) DANGEROUS AND HAZARDOUS

  • Open

    EL1833 — SECURE RACEWAY

    UNSUPPORTED CONDUITS AT EAST EXTERIOR LOT AREA SECURE CONDUITS WHERE REQUIRED THROUGHOUT PREMISES

  • Open

    EL1856 — SUPPORT OUTLET AND BOX

    UNSUPPORTED BOX AT EAST EXTERIOR LOT AREA SECURE BOXES WHERE REQUIRED THROUGHOUT PREMISES

  • Open

    EL1886 — Violation

    METER ENCLOSURE AND SERVICE RACEWAYS AT ALLEY NEED TO BE PROTECTED FROM PHYSICAL DAMAGE (14E-2-230.50)

  • Open

    EL1885 — Violation

    PROVIDE FULL DROP CEILING INSPECTION (14A-5-505.2)

  • Open

    EL1886 — Violation

    PROVIDE PERMIT TO CORRECT VIOLATIONS AND FOR THE INSTALLATION OF ELECTRICAL CONDUIT BOXES WIRE DEVICES AND EQUIPMENT FULL GUT REHAB OF SPACE/BUILDING AND NEW SERVICE NO PERMITS INSUFFICIENT PERMITS PREVIOUS PERMITS NO RECORD OF INSPECTIONS (14A-4-404.6)

  • Open

    EL1886 — Violation

    PROVIDE ANY REQUIRED ROUGH INSPECTION FOR THE INSTALLATION OF ELECTRICAL CONDUIT BOXES WIRE DEVICES AND EQUIPMENT FULL GUT REHAB OF SPACE/BUILDING AND NEW SERVICE NO PERMITS INSUFFICIENT PERMITS PREVIOUS PERMITS NO RECORD OF INSPECTIONS (14A-5-505.2)

  • Open

    CN067014 — REPAIR ROOF

    CEILING/ROOF AREAS WITHIN CAR WASH AREAS SPECIFICALLY AROUND PLUMBING STACK WHICH PERTRUDE THROUGH ROOF ROTTED AND MISSING SECTION OF ROOF MATERIAL REPAIRS REQUIRED

  • Open

    EL1801 — DEFECTIVE SERVICE

    DEBRIS AND STORAGE PILED ON SERVICE EQUIPMENT SERVICE EQUIPMENT SUBJECT WET CORROSIVE CONDITIONS ENSURE SERVICE IN APPROVED CONDITION DANGEROUS AND HAZARDOUS

  • Open

    EL1805 — DEFECTIVE DISTRIBUTION

    DEBRIS AND STORAGE LAYING ON DISTRIBUTION EQUIPMENT DISTRIBUTION EQUIPMENT SUBJECT TO WET CORROSIVE CONDITIONS ENSURE ALL DISTRIBUTION EQUIPMENT IN APPROVED CONDITION DANGEROUS AND HAZARDOUS

  • Open

    EL1806 — PROPER SIZE GRD ELECTRODE COND

    NO VISIBLE WATER GROUND ENSURE SERVICE GROUNDED IN APPROVED MANNER DANGEROUS AND HAZARDOUS

  • Open

    EL1809 — WORKING SPACE

    CLUTTER IN FRONT OF SERVICE AND DISTRIBUTION EQUIPMENT ENSURE WORKING SPACE THROUGHOUT DANGEROUS AND HAZARDOUS

  • Open

    EL1823 — INSTALL COVERS

    OPEN BOXES VARIOUS LOCATIONS AT INTERIOR OF CAR WASH AND CAR WASH OFFICE CLOSE OPEN BOXES THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1829 — EXPOSED WIRING

    OPEN WIRING AT VARIOUS LOCATIONS AT INTERIOR OF CAR WASH AND CAR WASH OFFICE REMOVE OPEN WIRING WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1866 — UNAPPROVED CORDS

    UNAPPROVED EXTENSION CORDS AT CAR WASH AREA UNAPPROVED CORD CONNECTIONS TO EQUIPMENT AT CAR WASH AREA DANGEROUS AND HAZARDOUS

  • Open

    EL1817 — CONTINUITY OF RACEWAYS

    DAMAGED TAPPED RACEWAY CONNECTION TO BOX AT CAR WASH AREA ENSURE GROUND CONTINUITY WHERE REQUIRED THROUGHOUT DANGEROUS AND HAZARDOUS

  • Open

    EL1839 — CORRODED CONDUIT & EQUIP

    CORRODED DISCONNECTS AND EQUIPMENT VISIBLE AREAS REPLACE CORRODED EQUIPMENT WHERE REQUIRED THROUGHOUT DANGEROUS AND HAZARDOUS

  • Open

    NC2021 — PERMIT REQUIRED - CONTRACTOR

    PERMITS REQUIRED FOR REPAIRS TO 50 X 100 GAS STATION/MERCHANTILE MASONRY BUILDING DUE TO VEHICULAR DAMAGE

  • Open

    IR0000 — SEND EX. METAL LETTER

  • Open

    IR0055 — PROTECT METAL MEMBERS

  • Open

    RF302021 — PRV RECEIVER

    450#PSIG FOR THE FOLLOWING ONE (1) 1/2 TON REMOTE REFRIGERATION UNIT LOCATED ON THE ROOF, THAT SERVES THE REACH IN COOLER.

About these City violation records

From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”

↑ Back to renter reviews

311 complaints (24 months)

  • building

    Building Violation

Timeline

  1. 311 building — Building Violation
  2. Open City violation record — EL1839 CORRODED CONDUIT & EQUIP
  3. Open City violation record — EL1817 CONTINUITY OF RACEWAYS
  4. Open City violation record — EL1866 UNAPPROVED CORDS
  5. Open City violation record — EL1829 EXPOSED WIRING
  6. Open City violation record — EL1823 INSTALL COVERS
  7. Open City violation record — EL1809 WORKING SPACE
  8. Open City violation record — EL1806 PROPER SIZE GRD ELECTRODE COND
  9. Open City violation record — EL1805 DEFECTIVE DISTRIBUTION
  10. Open City violation record — EL1801 DEFECTIVE SERVICE
  11. Open City violation record — CN067014 REPAIR ROOF
  12. Open City violation record — EL1886
  13. Open City violation record — EL1886
  14. Open City violation record — EL1885
  15. Open City violation record — EL1886
  16. Open City violation record — EL1856 SUPPORT OUTLET AND BOX
  17. Open City violation record — EL1833 SECURE RACEWAY
  18. Open City violation record — EL1884 SEE INSPECTOR COMMENTS
  19. Open City violation record — EL1827 RESTORE EXIT AND EM
  20. Open City violation record — EL1875 INSTALL GFCI'S
  21. Open City violation record — EL1817 CONTINUITY OF RACEWAYS
  22. Open City violation record — EL1816 ADD RECEPTACLES
  23. Open City violation record — EL1866 UNAPPROVED CORDS
  24. Open City violation record — EL1819 DEFECTIVE FIXTURES
  25. Open City violation record — EL1823 INSTALL COVERS
  26. Open City violation record — EL1829 EXPOSED WIRING
  27. Open City violation record — EL1836 PANEL SCHEDULES
  28. Open City violation record — EL1809 WORKING SPACE
  29. Open City violation record — EL1806 PROPER SIZE GRD ELECTRODE COND
  30. Open City violation record — EL1801 DEFECTIVE SERVICE
  31. Open City violation record — PL239010 ENGAG LIC & BOND PLMBNG CNTRC
  32. Open City violation record — PL232011 OBTAIN PERMIT FOR PLUMBING
  33. Open City violation record — PL237004 INDIRECT CONN.FOR WATER SUPPLY
  34. Open City violation record — CN197089 CARB MONOX DETECT IN ASSEMBLY
  35. Open City violation record — CN067014 REPAIR ROOF
  36. Open City violation record — CN194019 REPAIR OR REPLACE
  37. Open City violation record — CN031013 FIRE EXTNGSHR REQ, RESDNTL
  38. Open City violation record — EL1885
  39. Open City violation record — EL1884 SEE INSPECTOR COMMENTS
  40. Open City violation record — EL1819 DEFECTIVE FIXTURES

Recently closed / other violations (sample)

  • Closed / other

    RF301031 ACCESS TO ROOF

  • Closed / other

    RF301041 ARRANGE FOR INSPECTION

Around 823 N Western Ave

Nearby buildings with open City violation records

Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.

How the winter score is calculated
  1. Start at 100 (better = higher).
  2. Minus up to 40 for open heat/boiler-related building violations (12 pts each).
  3. Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
  4. Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
  5. Minus up to 15 for recent 311 building complaints (2 pts each).
  6. Extra −10 if 3+ open heat-related violations.
  7. Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
  8. Public records only — not an inspection, appraisal, or legal advice.

Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 22, 2026 at 1:36 AM CT.

ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.

“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.

Check another address

Help: hello@scoutmybuilding.com