6000 N Kenmore Ave
Winter habitability score Many open City violation records and/or complaint activity
Renter reviews
Firsthand and anonymous. Renter opinions are separate from the city records below.
No renter reviews here yet. If you’ve lived at 6000 N Kenmore Ave, yours could be the first.
Do you live here?
One tap helps other renters. The full building record stays right below.
Thanks for looking. The full record is right below.
No problem. The full record is right below.
Thanks, neighbor. Share how it’s really been — one tap on the stars is all it takes.
Thanks. Share how it really was — one tap on the stars is all it takes.
Sure, I’ll share
All open City violation records (61)
No open City violation records dated in the last 24 months (since November 2024). The newest open one is from February 5, 2020. All 61 are collapsed below — still open, still counted.
Show 61 older open City violation records (before November 2024)
- Open
CN190019 — ARRANGE PREMISE INSPECTION
INTERIOR OF BUILDING- NO RESPONSE,UNVERIFIED DETECTORS. UNVERIFIED COMPLAINT OF APT. #101-BED BUGS.
- Rodent-related
CN134016 — RATS
FRONT ELEVATION AROUND THE FOUNDATION,RAT HOLES OBSERVED.
- Open
CN190029 — ARRANGE FOR REINSPECTION REGAR
INTERIOR OF BUILDING /NO RESPONSE. UNABLE TO VERIFY DETECTORS AND CONDITIONS. UNVERIFIED COMPLAINTS SR#182776896 /APT. 201 - SMOKE DETECTORS LOW BATTERY. SR#182773312 /APT.103 - MICE AND BED BUGS.
- Open
CN190019 — ARRANGE PREMISE INSPECTION
INTERIOR OF BUILDING- NO RESPONSE,UNVERIFIED DETECTORS AND CONDITIONS.
- Open
CN196029 — POST OWNER/MANAGERS NAME/#
BUILDING- NO OWNER'S ID SIGN POSTED.
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
6002 N. / APARTMENT G2 - WALLS AND CEILINGS FLAKING PAINT AND PLASTER SEVERE .BATHROOM TUB AREA TILE WALL SECTION LOOSE AND MISSING TILES .
- Open
CN103015 — REPAIR FLOOR
6002 N. / APARTMENT G2 - BATHROOM LOOSE AND MISSING FLOOR TILES .
- Open
PL157047 — STOP LEAKING WATER
6002 N. / APARTMENT G2 - WATER LEAKING FROM ABOVE BATHTUB .
- Open
PL159017 — REPLACE DEFECTIVE PLBG FIXTURE
6002 N. / APARTMENT G2 - BATHROMM VANITY CABINATE BROKEN AND WATER DAMAGED .
- Open
CN014012 — NO CLOSET/STORAGE UNDER STAIR
BASEMENT AT BASE OF STAIRS , JUNK AND DEBRIS PILED UNDER STAIRS .
- Open
CN101025 — INT WALL/CEILING CHIP PLASTER
REAR STAIR HALLS , BROKEN PLASTER , UNPAINTED PREVIOUS PATCH WORK .
- Open
CN132046 — SAFE WORKING CONDITIONS
6002 N. / APARTMENT G2 - ALL BASEBOARD HEATERS COVERS BROKEN AND LOOSE . AND IN THROUGH CORRIDORS .
- Open
CN106015 — REPAIR INTERIOR STAIR SYSTEM
REAR STAIR HALLS , WORN TREADS .
- Open
PL159057 — STOP ODORS RPR DFT SEWAGE SYS
6002 N. / BASEMENT ELECTRICAL METER ROOM , SEVERE SEWER ODORS .
- Open
CN133016 — CARPETING
BUILDING - CARPETING ON STAIRS AND HALLS DIRTY AND UNSANITARY , ODORS .
- Open
CN190019 — ARRANGE PREMISE INSPECTION
BUILDING RESONSE OR ENTRY TO VERIFY COMPLAINT OF BED BUGS UNIT 103 OR REINSPECTION OF VIOLATIONS 3.9.2011.
- Open
CN198019 — FILE BLDG REGISTRATION
PROVIDE EVIDENCE OF BUILDING REGISTRATION FOR YEARS 1990- 2011.
- Open
CN138106 — STOP/REMOVE NUISANCE
FRONT AND FRONT AREAWAY AND REAR- ALL FLOORS, LOOSE, TANGLED ,HANGING PHONE AND CABLE LINES ,OPEN CABINATES. REAR LOT , ABANDON AUTO, (GOLD ) NISSAN, ALTIMA. SITTING IN REAR LOT FOR OVER TWO YEARS WITHOUT CURRENT PLATES OR VEHICLE STICKER .
- Open
CN131026 — REPAIR SCREENS
FRONT , FRONT AREAWAY AND REAR, ALL FLOORS, LOOSE ,MISSING SCREENS.
- Open
CN136026 — INSECTS
BUILDING-BED BUG INFESTATION THROUGHOUT. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION.
- Open
CN138106 — STOP/REMOVE NUISANCE
FRONT AND FRONT AREAWAY AND REAR- ALL FLOORS, LOOSE, TANGLED ,HANGING PHONE AND CABLE LINES ,OPEN CABINATES. REAR LOT , ABANDON AUTO, (GOLD ) NISSAN, ALTIMA.
- Open
NC2011 — PLANS & PERMITS REQ - CONTRCTR
REAR OF LOT- 30 BY 12 FOOT HIGH CHAINLINK ELECTRIFIED ROLLING DRIVEWAY GATE REQUIRES PLANS AND PERMITS.
- Open
CN136026 — INSECTS
BUILDING-BED BUG INFESTATION THROUGHOUT. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION. SECOND CASE WRITTEN FOR AH TARGET CALL . SEVERE INFESTATION ... BEDBUGS CRAWLING ON WALLS, IN CORNERS AND DOOR JAMBS. ENTIRE BUILDING REQUIRES TREATMENT . APARTMENT 6002 N. / G2 BLOOD SPOTS ON ALL WALLS WHERE TENANTS HAVE BEEN KILLING BEDBUGS .
- Open
NC2011 — PLANS & PERMITS REQ - CONTRCTR
REAR OF LOT- 30 BY 12 FOOT HIGH CHAINLINK ELECTRIFIED ROLLING DRIVEWAY GATE REQUIRES PLANS AND PERMITS. PERMIT # 100420975 ISSUED 12/5/2011 FO0R 6 FOOT TALL CHAINLINK FENCE NOT APPLICABLE FOR OVERSIZED COMMERCIAL GATE AND FENCE.
- Open
CN105015 — REPAIR DOOR, INT.
2ND FLLOR DOOR WONT CLOSE PROPERLY.
- Open
CN198019 — FILE BLDG REGISTRATION
NOT REGISTERED FROM 1990 THRU 2009.
- Open
EL0025 — SYSTEM III
IN ALL STAIRWAYS CORRIDORS AND COMMON AREAS OF BUILDING PROVIDE BATTERY BACK UP EXIT SIGNS AND ADD EM LIGHTS IN CORRIDORS-FLOORS 1-3
- Open
EL0044 — FIRE & WATER DAMAGE
FLOORS 1THUR3 FIRE AND WATER DAMAGE
- Open
EL0084 — SEE INSPECTOR COMMENTS
PROVIDE THE REQUIRED DIAGRAM AND LOAD CALCULATIONS FOR FEEDERS SERVICES AND REQUIRED EQUIPMENT-18327-215.5
- Open
EL0001 — DEFECTIVE LIGHTING SERVICE
DETERIORATE CABLES AT SERVICE HEAD
- Open
EL0010 — TENANT ACCESS TO SERVICE
NO ACCESS TO MAIN ELECTRICAL ROOM
- Open
CN104015 — REPLCE WINDOW PANES, PLEXGLAS
EAST ELEVATION AND EAST COURT YARD BROKEN WINDOWS 2ND AND 3RD FLOORS WEST ELEVATION AT 2 AND 3 SOUTH END
- Open
CN131026 — REPAIR SCREENS
MISSING AND BROKEN SCREENS THRU OUT
- Open
CN065014 — REPAIR LINTELS
RUSTING LINTELS EAST ELEVATION AND COURTYARD WEST ELEVATION
- Open
CN067024 — REPAIR EAVES
ROTTING EAVES SOFFIT AND FASCIA COURTYARD AT DOWNSPOUTS AND WEST ELEVATION DAMAGED WOOD TOWARD SOUTH END
- Open
CN065034 — REPAIR WINDOW SILLS
OPEN SILL JOINTS THRU OUT BUILDING
- Open
CN061034 — FLAKY INTERIOR PAINT
FLAKING PAINT 6000 AND 6002 FRONT ENTRIES ROOF SOFFITS AND FRAMING
- Open
CN074014 — SERVICE WALK, PASSAGE, AREAWAY
6000 FRONT SERVICE WALK FRACTURES
- Open
CN061014 — REPAIR EXTERIOR WALL
ERODING MORTAR LOOSE MORTAR FRACTURES WEST ELEVATION FRACTURED CONCRETE AND EXPOSED IRON MESH AT REAR GARAGE HEADER FRACTURES AT BRICK AT NORTH AND SOUTH ENDS OF GARAGE HEADER AND EXPOSED IRON MISSING MORTAR MASONRY FRACTURES AT REAR 6000 ENTRY
- Open
CN107015 — ILLUMINATE PUBLIC STAIR/HALL
EMERGENCY LIGHTS NOT OPERATING THRU OUT 6000 BUILDING AND AT 6002 BASEMENT CORRIDOR AND 1ST FLOOR CORRIDOR
- Open
CN140016 — DWELLING CLEAN AND SANITARY
6000 FRONT ENTRY PAPERS GARBAGE
- Open
CN133016 — CARPETING
6000 UNSANITARY CARPETS THRU OUT FIRE DAMAGE DEBRIS
- Open
CN073014 — REPAIR EXTERIOR DOOR
6000 STAIRWELL DOORS FIRE DAMAGED AND BROKEN UNIT DOORS DAMAGED BY FIRE THRU OUT 2ND FLOOR AND VARIOUS OTHER LOCATIONS THRU OUT FIRE DAMAGE DEBRIS
- Open
CN138106 — STOP/REMOVE NUISANCE
EAST SIDE OF BUILDING AND COURT YARD BROKEN GLASS AND SCREENS THRU OUT YARD
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
6000 FIRE DAMAGED WALLS AND CEILINGS ALSO WATER DAMAGE MOST SIGNIFICANT ON 2ND AND 3RD FLOORS
- Open
CN103015 — REPAIR FLOOR
6000 FIRE DAMAGED FLOORS AND WATER DAMAGE MOST SIGNIFICANT ON 2ND AND 3RD FLOORS
- Open
CN107035 — MAINTAIN EXIT SIGN ILLUMINATED
6000 EXIT SIGNS NOT LIT THRU OUT
- Open
CN031023 — FIRE EXTNGSHR RECHARGE & TAG
6002 REAR STAIRWELL AT GROUND FIRE EXTINGUISHER NEED CHARGE AND TAGS
- Open
CN197087 — CARB MONOX DETECT IN RESID
6002 BASEMENT LAUNDRY ROOM NO CARBON MONOXIDE DETECTOR
- Open
NC2022 — BLANK-TEXT MUST CITE CODE SECT
6002 BOILER ROOM CEILING HOLES AND OPENING IN DRYWALL EXPOSED WOOD
- Heat-related
CN011012 — HEATING PLANT/BOILER ROOM DOOR
6002 BOILER ROOM DOOR ONLY FIRE RATED 30 MINUTES
- Open
CN015062 — OBSTRUCTIONS IN EXIT WAY
6002 STAIRWELL DOORS ALL LOCKED FROM STAIRWELL SIDE
- Open
CN197019 — INSTALL SMOKE DETECTORS
NO SMOKE DETECTORS 6002 UNIT 203, 301
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
SMOKE DETECTORS NOT OPERATING UNIT 303 IN 6002 AND REAR STAIRWELL AT 6002
- Open
CN070014 — REPAIR EXTERIOR STAIR
FRONT AND REAR STAIRWELLS IMPROPER RAILING DESIGN AND PICKET SPACING
- Open
NC2021 — PERMIT REQUIRED - CONTRACTOR
OBTAIN PERMITS FOR FIRE DAMAGE REPAIRS AND ROOF REPAIRS
- Open
CN103015 — REPAIR FLOOR
ADDITIONAL INFORMATION: FLOORCOMMENTS: BROKEN FLOOR TILE AT FOYER 6000.
- Open
CN067024 — REPAIR EAVES
EAVES ROTTED NEAR GUTTER DOWNSPOUTS 6000 & 6002.
- Open
CN138026 — USE SANITARY REFUSE CONTAINERS
FOOD GARBAGE ON REAR STAIRS AT 6000.
- Open
CN140016 — DWELLING CLEAN AND SANITARY
GARBAGE IN REAR STAIRWAY AT 6000.
- Open
CN133016 — CARPETING
CARPET FRAYED GRADE TO 3RD, STAIRWAY AT 6000.
About these City violation records
From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”
311 complaints (24 months)
- building
Building Violation
- building
Buildings - Plumbing Violation
- building
Building Violation
Timeline
- 311 building — Building Violation
- 311 building — Building Violation
- 311 building — Buildings - Plumbing Violation
- Open City violation record — CN134016 RATS
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — CN190029 ARRANGE FOR REINSPECTION REGAR
- Open City violation record — CN196029 POST OWNER/MANAGERS NAME/#
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — CN133016 CARPETING
- Open City violation record — PL159057 STOP ODORS RPR DFT SEWAGE SYS
- Open City violation record — CN106015 REPAIR INTERIOR STAIR SYSTEM
- Open City violation record — CN132046 SAFE WORKING CONDITIONS
- Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
- Open City violation record — CN014012 NO CLOSET/STORAGE UNDER STAIR
- Open City violation record — PL159017 REPLACE DEFECTIVE PLBG FIXTURE
- Open City violation record — PL157047 STOP LEAKING WATER
- Open City violation record — CN103015 REPAIR FLOOR
- Open City violation record — CN101015 REPAIR INTERIOR WALLS/CEILING
- Open City violation record — CN198019 FILE BLDG REGISTRATION
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — NC2011 PLANS & PERMITS REQ - CONTRCTR
- Open City violation record — CN136026 INSECTS
- Open City violation record — NC2011 PLANS & PERMITS REQ - CONTRCTR
- Open City violation record — CN138106 STOP/REMOVE NUISANCE
- Open City violation record — CN136026 INSECTS
- Open City violation record — CN131026 REPAIR SCREENS
- Open City violation record — CN138106 STOP/REMOVE NUISANCE
- Open City violation record — CN198019 FILE BLDG REGISTRATION
- Open City violation record — CN105015 REPAIR DOOR, INT.
- Open City violation record — EL0010 TENANT ACCESS TO SERVICE
- Open City violation record — EL0001 DEFECTIVE LIGHTING SERVICE
- Open City violation record — EL0084 SEE INSPECTOR COMMENTS
- Open City violation record — EL0044 FIRE & WATER DAMAGE
- Open City violation record — EL0025 SYSTEM III
- Open City violation record — NC2021 PERMIT REQUIRED - CONTRACTOR
- Open City violation record — CN070014 REPAIR EXTERIOR STAIR
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — CN197019 INSTALL SMOKE DETECTORS
- Open City violation record — CN015062 OBSTRUCTIONS IN EXIT WAY
- Open heat-related City violation record — CN011012 HEATING PLANT/BOILER ROOM DOOR
Recently closed / other violations (sample)
- Closed / other
CN190019 ARRANGE PREMISE INSPECTION
- Closed / other
CN101025 INT WALL/CEILING CHIP PLASTER
- Closed / other
CN198019 FILE BLDG REGISTRATION
- Closed / other
PL157047 STOP LEAKING WATER
- Closed / other
CN132046 SAFE WORKING CONDITIONS
- Closed / other
CN014012 NO CLOSET/STORAGE UNDER STAIR
- Closed / other
CN106015 REPAIR INTERIOR STAIR SYSTEM
- Closed / other
CN101015 REPAIR INTERIOR WALLS/CEILING
- Closed / other
CN103015 REPAIR FLOOR
- Closed / other
PL159017 REPLACE DEFECTIVE PLBG FIXTURE
- Closed / other
CN132016 HEAT UNIT ADEQUATELY
- Closed / other
CN104025 MAINTAIN WINDOW SASH
- Closed / other
CN061014 REPAIR EXTERIOR WALL
- Closed / other
CN077014 REPAIR FENCE
- Closed / other
CN138026 USE SANITARY REFUSE CONTAINERS
- Closed / other
CN196029 POST OWNER/MANAGERS NAME/#
- Closed / other
NC2010 PLANS & PERMITS REQUIRED
- Closed / other
CN104025 MAINTAIN WINDOW SASH
- Closed / other
CN138026 USE SANITARY REFUSE CONTAINERS
- Closed / other
CN138106 STOP/REMOVE NUISANCE
- Closed / other
CN196029 POST OWNER/MANAGERS NAME/#
- Closed / other
NC2010 PLANS & PERMITS REQUIRED
- Closed / other
CN198019 FILE BLDG REGISTRATION
- Closed / other
CN105015 REPAIR DOOR, INT.
- Closed / other
CN198019 FILE BLDG REGISTRATION
Around 6000 N Kenmore Ave
- Edgewater community area: search another address
- No heat in your Chicago apartment? The heat ordinance and what to do
Nearby buildings with open City violation records
Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.
How the winter score is calculated
- Start at 100 (better = higher).
- Minus up to 40 for open heat/boiler-related building violations (12 pts each).
- Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
- Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
- Minus up to 15 for recent 311 building complaints (2 pts each).
- Extra −10 if 3+ open heat-related violations.
- Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
- Public records only — not an inspection, appraisal, or legal advice.
Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 2:50 PM CT.
ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.
“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.