Free building report

550 W WEBSTER AVE

Winter habitability score Many open City violation records and/or complaint activity

Download a PDF of this report

Renter reviews

Firsthand and anonymous. Renter opinions are separate from the city records below.

No renter reviews here yet. If you’ve lived at 550 W Webster Ave, yours could be the first.

A Chicago three-flat

Do you live here?

One tap helps other renters. The full building record stays right below.

Sure, I’ll share
How’s it been living here? Required

Tap a star — 1 is rough, 5 is great.

Add more detail (optional — heat, pests, repairs, noise, management)

Tap 1 to 5 for any you want. 1 is rough, 5 is great. Skip the rest.

Heat Warm enough when it counts?
Pests Have pests been a problem?
Maintenance responsiveness When something broke, how fast did it get fixed?
Noise How noisy was it, day to day?
Management How they treated you and answered you
Would you rent here again?

Your own experience only — no fake or paid reviews. Shown anonymously after you confirm and a person approves it. Review policy · Terms

43Open City violation records
5Open heat-related City records
0311 rodent (24 mo)
1311 building (24 mo)

What rat complaints mean →

All open City violation records (43)

No open City violation records dated in the last 24 months (since November 2024). The newest open one is from April 21, 2010. All 43 are collapsed below — still open, still counted.

Show 43 older open City violation records (before November 2024)
  • Open

    CN073054 — REPAIR EXTERIOR DOOR, RESET

    DOORS (1)FORMER RESTURANT DOOR DAMAGED REPAIR/REMOVE (2) SOUTH ELEVATION DOORS NEXT TO EMERGENCY ENTRANCE DOUBLE DOORS OPEN NOT PROPERLY SECURED

  • Open

    NC2020 — PERMIT REQUIRED

    PROVIDE PERMIT FOR INSTALLATION OF FENCE ALONG NORTH ELEVATION OF BUILDING, SURROUNDING BACK PARKING AREA AND REAR OF BUILDING

  • Open

    CN060001 — SUBMIT 2 COPIES CRITICAL EXAM

    HAS NOT SUBMITTED EXAM AS REQUIRED PER ORDINANCE

  • Open

    CN061014 — REPAIR EXTERIOR WALL

    EXTERIOR WALL REPAIR - (1) SOUTH ELEVATION SEVERE CONCRETE DAMAGE ABOVE FORMER EMERGENCY ENTRANCE/EXIT (2) UNDERSIDE OF ENTRANCE OF FORMER HOSPITAL LOOSE LIGHT FIXTURES DANGEROUS (3) PERMITS FOR MASONRY REPAIRS

  • Open

    CN193339 — POST OWNER COMM VACNT BLDG

    POST PROPER OWNERSHIP/MANAGEMENT INFORMATION (NO P.O.BOX) OF VACANT BUILDING

  • Open

    CN193110 — VACANT BUILDING - REGISTER

    MUST INSURE VACANT BUILDING

  • Open

    CN193105 — VACANTBUILDING-REGISTER/SECURE

    MUST REGISTER VACANT BUILDING

  • Open

    CN060001 — SUBMIT 2 COPIES CRITICAL EXAM

    DID NOT FILE CRITICAL EXAMINATION DUE NOT LATER THAN 12/1/2008 AS OF JANUARY 20, 2010. IF THE BUILDING IS OCCUPIED AND HAZARDOUS CONDITIONS DO NOT EXIST ON THE BUILDING, OWNERS MAY TAKE ADVANTAGE OF THE REDUCED INSPECTION COVERAGE IN AMENDED RULES AND REGULATIONS PUT IN EFFECT OCTOBER 22, 2009 AND MAY FILE ONGOING MAINTENCE AND REPAIR REPORT "SHORT FORMS" EVERY SECOND YEAR AFTER SUBMITTING A CURRENT CRITICAL EXAMINATION. CALL ALLISON SULLIVAN AT 312-743-3522 WITH QUESTIONS.

  • Open

    199029 — OPEN TYPE VIOLATION

    PERFORM ANNUAL PRESSURE RELIEF AND HYDRAULIC SYSTEM TEST. TAG VALVE SUBMIT RESULTS TO ELEVATOR BUREAU (A17.1A-1997 RULE 1005.2A)

  • Open

    BR3054 — REPAIR

    REPAIR OR REPLACE BLOW DOWN VALVE ON ERIE BOILER.

  • Open

    BR3054 — REPAIR

    REPAIR OR REPLACE LEAK ON RIGHT FRONT SIDE ON ERIE BOILER.

  • Open

    BR3055 — REPLACE

    OR REPAIR STEAM HEADER VALVE ON ERIE BOILER.

  • Open

    BR1001 — OWNER OR LICENSED CONTRACTOR

  • Heat-related

    BR1063 — LEAKING BOILER TUBES

    ERIE BOILER.

  • Heat-related

    BR1010 — DEFECTIVE SAFETY VALVE-BOILER

    REPAIR OR REPLACE SAFETY VALVES ON ERIE BOILER.

  • Open

    BR3058 — SEE INSPECTOR COMMENTS

    #2 ERIE -KEYSTONE BOILER NATL BOILER BD#98385 TURBING ALL BOILER TUBES.

  • Heat-related

    BR2060 — ADJUST BOILER BURNER

    #2 ERIE -KEYSTONE BOILER NATL BOILER BD#98385.

  • Open

    BR2021 — HYDROSTATIC TEST

    #2 ERIE -KEYSTONE BOILER NATL BOILER BD#98385.

  • Open

    BR2020 — CERTIFICATE OF OPERATION

    #2 ERIE CITY BOILER. BLDG 28

  • Open

    BR1001 — OWNER OR LICENSED CONTRACTOR

  • Open

    BR2080 — INTERNAL

    #1 ECI HIGH PRESSURE BOILER N.B. 98384.

  • Open

    BR2080 — INTERNAL

    #2 ERIC CITY BOILER NATL BD #98385.

  • Open

    BR2080 — INTERNAL

    #3 ANDEE BOILER NATL BD #1.

  • Open

    BR3058 — SEE INSPECTOR COMMENTS

    ENGAGE IN A LISCENSE BOILER CONTRACTOR TO REPAIR OR REPLACE LEAKING DEAIRATOR TANK.

  • Heat-related

    BR1010 — DEFECTIVE SAFETY VALVE-BOILER

    #2 ERIE CITY HIGH PRESSURE BOILER. BLDG 28.

  • Heat-related

    BR1010 — DEFECTIVE SAFETY VALVE-BOILER

    #3 ERIE CITY HIGH PRESSURE BOILER. BLDG 28.

  • Open

    BR3057 — INSTALL

    CARBON MONOXIDE DETECTOR. BUILDING 28

  • Open

    BR3055 — REPLACE

    LEAKING HEAT EXCHANGER. BLDG 28

  • Open

    BR3055 — REPLACE

    REPLACE LEAKING PIPING AND PRV VALVE. BLDG 28

  • Open

    BR3055 — REPLACE

    REPLACE CHILL WATER RETURN VALVE. BLDG 28

  • Open

    BR3055 — REPLACE

    REPLACE PIPING AND COPES VALUE AND UNION ON #2 ERIE CITY BOILER. BLDG 28

  • Open

    BR3054 — REPAIR

    OR REPLACE LEAKING FEED STEAM LINE. BLDG 63

  • Open

    BR2020 — CERTIFICATE OF OPERATION

    #3 ERIE CITY BOILER. BLDG 28

  • Open

    RF301051 — ARRANGE FOR RE-INSPECTION

    CONTACT INSPECTOR STEPHEN MCGANN #971 @ 312-44-5390 OR 312-743-6562.

  • Open

    RF301011 — OBTAIN REFRIGERATION PERMIT

    RE: FOR ALL A/C AND REFRIGERATION EQUIPMENT LISTED ABOVE.

  • Open

    NC2011 — PLANS & PERMITS REQ - CONTRCTR

    RE: ONE 18 TON A/C UNIT LOCATED IN BUILDING 1975, COMPUTER ROOM. (AFX65M-GKA-ESU) ONE 15 TON CARRIER A/C UNIT LOCATED IN BUILDING 1975, PHARMACY. ONE 3 TON LIEBERT A/C UNIT LOCATED IN BUILDING 1975, MRI-AREA. ONE 55 TON CARRIER A/C UNIT LOCATED ON ROOF OF E.R., 1963 BUILDING.

  • Open

    RF302091 — CONNECT VENT LINE

    RE: TWO TECUMSEH COMPRESSORS, SERVING THE WALK-IN COOLERS IN THE MORGUE.

  • Open

    RF302021 — PRV RECEIVER

    RE: TWO TECUMSEH COMPRESSORS, SERVING THE WALK-IN-COOLERS IN THE MORGUE.

  • Open

    CN061000 — LIFE SAFETY EVALUATION PLAN

    LIFE SAFETY EVALUATION DUE JANUARY 1, 2006 HAS NOT BEEN SUBMITTED AS OF JUNE 20, 2006 CALL JOSE APARICIO 312/743-7266

  • Open

    BR2080 — INTERNAL

    #1 ECI HIGH PRESSURE BOILER N.B. 98384.

  • Open

    BR2080 — INTERNAL

    #3 ANDEE BOILER NATL BD #1.

  • Open

    BR2080 — INTERNAL

    #2 ERIC CITY BOILER NATL BD #98385.

  • Open

    BR1001 — OWNER OR LICENSED CONTRACTOR

About these City violation records

From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”

↑ Back to renter reviews

311 complaints (24 months)

  • building

    Vacant/Abandoned Building Complaint

Timeline

  1. 311 building — Vacant/Abandoned Building Complaint
  2. Open City violation record — CN193105 VACANTBUILDING-REGISTER/SECURE
  3. Open City violation record — CN193110 VACANT BUILDING - REGISTER
  4. Open City violation record — CN193339 POST OWNER COMM VACNT BLDG
  5. Open City violation record — CN061014 REPAIR EXTERIOR WALL
  6. Open City violation record — CN060001 SUBMIT 2 COPIES CRITICAL EXAM
  7. Open City violation record — NC2020 PERMIT REQUIRED
  8. Open City violation record — CN073054 REPAIR EXTERIOR DOOR, RESET
  9. Open City violation record — CN060001 SUBMIT 2 COPIES CRITICAL EXAM
  10. Open City violation record — 199029 OPEN TYPE VIOLATION
  11. Open heat-related City violation record — BR1010 DEFECTIVE SAFETY VALVE-BOILER
  12. Open heat-related City violation record — BR1063 LEAKING BOILER TUBES
  13. Open City violation record — BR1001 OWNER OR LICENSED CONTRACTOR
  14. Open City violation record — BR3055 REPLACE
  15. Open City violation record — BR3054 REPAIR
  16. Open City violation record — BR3054 REPAIR
  17. Open City violation record — BR2021 HYDROSTATIC TEST
  18. Open heat-related City violation record — BR2060 ADJUST BOILER BURNER
  19. Open City violation record — BR3058 SEE INSPECTOR COMMENTS
  20. Open City violation record — BR2020 CERTIFICATE OF OPERATION
  21. Open City violation record — BR3054 REPAIR
  22. Open City violation record — BR3055 REPLACE
  23. Open City violation record — BR3055 REPLACE
  24. Open City violation record — BR3055 REPLACE
  25. Open City violation record — BR3055 REPLACE
  26. Open City violation record — BR3057 INSTALL
  27. Open heat-related City violation record — BR1010 DEFECTIVE SAFETY VALVE-BOILER
  28. Open heat-related City violation record — BR1010 DEFECTIVE SAFETY VALVE-BOILER
  29. Open City violation record — BR3058 SEE INSPECTOR COMMENTS
  30. Open City violation record — BR2080 INTERNAL
  31. Open City violation record — BR2080 INTERNAL
  32. Open City violation record — BR2080 INTERNAL
  33. Open City violation record — BR1001 OWNER OR LICENSED CONTRACTOR
  34. Open City violation record — BR2020 CERTIFICATE OF OPERATION
  35. Open City violation record — RF302021 PRV RECEIVER
  36. Open City violation record — RF302091 CONNECT VENT LINE
  37. Open City violation record — NC2011 PLANS & PERMITS REQ - CONTRCTR
  38. Open City violation record — RF301011 OBTAIN REFRIGERATION PERMIT
  39. Open City violation record — RF301051 ARRANGE FOR RE-INSPECTION
  40. Open City violation record — CN061000 LIFE SAFETY EVALUATION PLAN

Recently closed / other violations (sample)

  • Closed / other

    CN193339 POST OWNER COMM VACNT BLDG

  • Closed / other

    CN073054 REPAIR EXTERIOR DOOR, RESET

  • Closed / other

    CN061014 REPAIR EXTERIOR WALL

  • Closed / other

    CN060001 SUBMIT 2 COPIES CRITICAL EXAM

  • Closed / other

    NC2020 PERMIT REQUIRED

  • Closed / other

    199029 OPEN TYPE VIOLATION

  • Closed / other

    BR3055 REPLACE

  • Closed / other

    BR3055 REPLACE

  • Closed / other

    BR3055 REPLACE

  • Closed / other

    BR3055 REPLACE

  • Closed / other

    BR2052 INSTALL RELIEF VALVE - HWH

Around 550 W Webster Ave

Nearby buildings with open City violation records

Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.

How the winter score is calculated
  1. Start at 100 (better = higher).
  2. Minus up to 40 for open heat/boiler-related building violations (12 pts each).
  3. Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
  4. Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
  5. Minus up to 15 for recent 311 building complaints (2 pts each).
  6. Extra −10 if 3+ open heat-related violations.
  7. Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
  8. Public records only — not an inspection, appraisal, or legal advice.

Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 9:13 AM CT.

ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.

“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.

Check another address

Help: hello@scoutmybuilding.com