Free building report

5201 S CORNELL AVE

Winter habitability score Multiple habitability signals in public records

Download a PDF of this report

Renter reviews

Firsthand and anonymous. Renter opinions are separate from the city records below.

No renter reviews here yet. If you’ve lived at 5201 S Cornell Ave, yours could be the first.

A Chicago three-flat

Do you live here?

One tap helps other renters. The full building record stays right below.

Sure, I’ll share
How’s it been living here? Required

Tap a star — 1 is rough, 5 is great.

Add more detail (optional — heat, pests, repairs, noise, management)

Tap 1 to 5 for any you want. 1 is rough, 5 is great. Skip the rest.

Heat Warm enough when it counts?
Pests Have pests been a problem?
Maintenance responsiveness When something broke, how fast did it get fixed?
Noise How noisy was it, day to day?
Management How they treated you and answered you
Would you rent here again?

Your own experience only — no fake or paid reviews. Shown anonymously after you confirm and a person approves it. Review policy · Terms

59Open City violation records
1Open heat-related City records
0311 rodent (24 mo)
0311 building (24 mo)

What rat complaints mean →

All open City violation records (59)

3 of 59 open City violation records are from the last 24 months (since November 2024), shown newest first. 56 older ones are collapsed below — still open, still counted.

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    MAKE PROPER REPAIRS TO FIRE SERVICE OPERATION ON ALL ELEVATORS

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    REPLACE ROUGING CABLES ON ELEVATOR 2S.

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    DIAGRAMMATIC REPRESENTATION SHALL BE DISPLAYED AT LOBBY PANEL

Show 56 older open City violation records (before November 2024)
  • Open

    CN190029 — ARRANGE FOR REINSPECTION REGAR

    5201 S. / APARTMENT # 15B - NO ENTRY, UNVERIFIED CONDITIONS AND DETECTORS; UNABLE TO VERIFY COMPLAINT OF APARTMENT INFESTED WITH FLIES, DUE TO TENANT BEING A HOARDER; BAD STENCH; CREATING A RODENT PROBLEM.

  • Open

    CN197079 — REPAIR/REPLACE SMOKE DETECTORS

    LAUNDRY ROOM / SMOKE DETECTOR - OUT OF SERVICE AT TIME OF INSPECTION.

  • Open

    CN197087 — CARB MONOX DETECT IN RESID

    LAUNDRY ROOM / CARBON MONOXIDE DETECTOR - OUT OF SERVICE AT TIME OF INSPECTION.

  • Open

    EL0019 — DEFECTIVE FIXTURES

    MULTIPLE LOCATIONS / EXIT SIGNS - NOT ILLUMINATED AT TIME OF INSPECTION.

  • Open

    CN106015 — REPAIR INTERIOR STAIR SYSTEM

    28 FL / STAIRS LEADING TO BOILER ROOM / HANDRAIL - LOOSE AT TOP CONNECTION.

  • Open

    PL154027 — SUPPLY HOT WTR MIN TEMP 120DEG

    BATHROOM AT GRADE AND UNIT 7B / HOT WATER SUPPLIED AT ONLY 100F AT 1:00 PM.

  • Open

    CN073014 — REPAIR EXTERIOR DOOR

    EAST EXIT DOOR AT GROUND FLOOR NEAR BATHROOMS / DOOR IS DRAFTY WITH AIR SEEPAGE.

  • Open

    CN190019 — ARRANGE PREMISE INSPECTION

    INTERIOR OF MOST APTS. - NO RESPONSE, UNVERIIFED DETECTORS AND CONDITIONS.

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    INSTALL BRAILLE PLATES

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    PROVIDE FASCIA EXTENSIONS AS NEEDED TO REMOVE HAZARDS ABOVE HEADERS

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    PROVIDE CLIMATE CONTROL IN MACHINE ROOM

  • Open

    EV1110 — MAINTAIN OR REPAIR ELECT ELEVA

    LABEL CONTROLLER AND MACHINE

  • Open

    CN196029 — POST OWNER/MANAGERS NAME/#

    BUILDING - NO OWNER'S I.D. SIGN POSTED .

  • Open

    CN075014 — GRADE AND DRAIN LOT

    FRONT DRIVEWAY WORN AND WEATHERED PAVEMENT COATING .

  • Open

    NC6012 — 1HR PUB.CORRIDOR IN MULT. D.U.

    FIRST FLOOR MANAGEMENT OFFICE DOOR BEING HELD OPEN WITHOUT AUTOMATIC RELEASE OR FAILSAFE DEVICE .

  • Open

    CN101025 — INT WALL/CEILING CHIP PLASTER

    26TH FLOOR NORTH HALLWAY - TRASH ROOM , WALLS AND CEILING FLAKING PAINT .

  • Open

    NC5042 — SELF-CLOSE CLASS B FIRE DOOR

    26TH FLOOR NORTH HALLWAY - TRASH ROOM , TRASH CHUTE DOOR NOT AUTO CLOSING AND LATCHING .

  • Open

    CN197079 — REPAIR/REPLACE SMOKE DETECTORS

    26TH FLOOR NORTH ELEVATOR HALLWAY - SMOKE DETECTOR OUT OF SERVICE AT TIME OF INSPECTION .

  • Open

    CN102015 — INT WALL/CEILING PEELING PAINT

    FIRST FLOOR MANAGEMENT OFFICE CEILING WATER DAMAGED AND FLAKING .

  • Open

    CN075014 — GRADE AND DRAIN LOT

    FRONT DRIVEWAY WORN AND WEATHERED PAVEMENT COATING .

  • Open

    CN101015 — REPAIR INTERIOR WALLS/CEILING

    APARTMENT #26B - HALLWAY OUTSIDE BATHROOM , NORTH WALL DRYWALL REPAIRS FROM PIPE REPLACEMENT NOT COMPLETED TO FINISH PAINT . KITCHEN CEILING WATER DAMAGED AT EAST , WALLS PEELING WALLPAPER AT SEAMS . KITCHEN SINK BASE REAR WALL DRYWALL REPAIRS NOT COMPLETED .

  • Open

    CN197079 — REPAIR/REPLACE SMOKE DETECTORS

    26TH FLOOR NORTH ELEVATOR HALLWAY - SMOKE DETECTOR OUT OF SERVICE AT TIME OF INSPECTION .

  • Open

    CN102015 — INT WALL/CEILING PEELING PAINT

    FIRST FLOOR MANAGEMENT OFFICE CEILING WATER DAMAGED AND FLAKING .

  • Open

    PL159017 — REPLACE DEFECTIVE PLBG FIXTURE

    APARTMENT #26B - KITCHEN SINK BASE CABINET MISSING FLOOR IN CABINET .

  • Open

    CN197019 — INSTALL SMOKE DETECTORS

    APARTMENT #26B - SMOKE DETECTOR OUT OF SERVICE AND EXPIRED AT TIME OF INSPECTION .

  • Open

    NC6012 — 1HR PUB.CORRIDOR IN MULT. D.U.

    FIRST FLOOR MANAGEMENT OFFICE DOOR BEING HELD OPEN WITHOUT AUTOMATIC RELEASE OR FAILSAFE DEVICE .

  • Open

    CN101025 — INT WALL/CEILING CHIP PLASTER

    26TH FLOOR NORTH HALLWAY - TRASH ROOM , WALLS AND CEILING FLAKING PAINT .

  • Open

    NC5042 — SELF-CLOSE CLASS B FIRE DOOR

    26TH FLOOR NORTH HALLWAY - TRASH ROOM , TRASH CHUTE DOOR NOT AUTO CLOSING AND LATCHING .

  • Open

    CN194029 — PROVIDE

    COMPLETE CITY OF CHICAGO MACHINE ROOM FOR CHILLERS.

  • Open

    CN194029 — PROVIDE

    COMPLETE CITY OF CHICAGO MACHINE ROOM FOR PENTHOUSE CHILLER ROOM. REFRIGERANT SENSORS,MONITOR, AUDIBLE / VISIBLE ALARMS INSIDE AND OUTSIDE ROOM,SCBA OUTSIDE ROOM, REFRIGERANT EXHAUST FAN DUCTED 12" ABOVE FINISHED FLOOR, EMERGENCY SWITCH LOCATED OUSIDE OF ROOM TO ACTIVATE REFRIGERANT EXHAUST FAN AND SIGNAGE LOCATED ON MAIN ENTRY TO ROOM TO READ - HIGH PRESSURE REFRIGERANT -DANGER- IF LIGHT OR ALARM ON . DO NOT ENTER. AUTHORIZED PERSONNEL ONLY

  • Open

    CN190019 — ARRANGE PREMISE INSPECTION

    MOST UNIT DOORS, INCLUDING 3A, 3D, 3E, 4F, 5E, 6B, 7A, 7F, 7E, 8A, 8B, 9B, 9C, 9F, 10D, 11A, 11B, 11C, 11F, 11E, 12D, 14F, 14D,15A, 15B, 15E, 16A, 17B, 17E, 18A, 18E, 18F, 19C, 19F, 20A, 20C, 20D, 20F, 21A, 21B, 21D, 21F, 21E, 22D, 23A, 23C, 23F, 24F, 24E, 25C, 25D, 25E, 26D, 26E, 27A, 27B, 27C, 28C AND TOWNHOUSE 5115, 5117, 5119, 5125, 5127, 5131, 5145 AND 5147 REAR DOORS TO "SHARED GARAGE" WITH 5201 S. / BUILDING: NO RESPONSE - UNABLE TO VERIFY FIRE DOOR RATINGS, SELF-CLOSING AND LATCHING CONDITIONS.

  • Open

    EL0019 — DEFECTIVE FIXTURES

    INTERIOR STAIRWAYS: LLA, 2B, 3D, 5D, 8B, 24D AND 24E - EMERGENCY LIGHTS - BROKEN AND OUT OF SERVICE.

  • Open

    CN073054 — REPAIR EXTERIOR DOOR, RESET

    SOUTH TOWER PENTHOUSE - BOILER ROOM EXTERIOR FIRE DOOR TO ROOF - RUBBING ON SILL, WITH GAP AT TOP.

  • Open

    NC5042 — SELF-CLOSE CLASS B FIRE DOOR

    SOUTH ELEVATOR MACHINE ROOM LOCATED AT MEZZANINE FLOOR OPEN TO BOILER ROOM; SALT / LAWN MOWER / BLOWER STORAGE ROOM, FURNITURE ROOM AND SUPPLY ROOMS - DOORS AND FRAMES MISSING CLASS B LABELS. PENTHOUSE BOILER ROOM - FLOOR HATCH HOLE TO 28TH FLOOR HAS DETACHED NON FIRE RATED WOODEN DOOR; NORTH ELEVATOR MACHINE ROOM - PLYWOOD HOLLOW DOOR - CLASS B DOORS REQUIRED.

  • Heat-related

    CN043023 — 2 HOUR BOILER ENCLOSURE

    NORTH TOWER PENTHOUSE - SECTIONS OF DRYWALL MISSING NEAR THE AIR VENT SHAFT. SOUTH TOWER BOILER ROOM WITH TWO LARGE OPENINGS TO A LARGE HALLWAY, TRASH ROOM AND PUMP ROOM AT LOWER LEVEL OPENING THROUGH CORRIDOR ARE MISSING CLASS B DOORS. PERMIT REQUIRED TO INSTALL FIRE RATED DOORS.

  • Open

    CN044013 — PIPE OPENING W/NONCOMBUST MATL

    SCISSOR STAIRWELLS: MOST LANDINGS, INCLUDING 17A, 27D, 26D AND GAPS FROM 2ND THRU 3RD FLOOR STAIR FLIGHT, NORTH TOWER / 1ST FLOOR SUPPLY STORAGE ROOM, PENTHOUSE / NORTH BOILER ROOM 24"X30" AIR VENT SHAFT, ELEVATOR MACHINE ROOMS AND ELECTRIC METER ROOMS AT 7TH AND 27TH FLOORS - OPEN HOLES ON WALLS, FLOORS AND CEILINGS BY PIPING, CABLES, CONDUITS AND VENT SHAFTS. SOME OF THE PIPE AND CABLE PENETRATION HOLES SEALED WITH CEMENT, SPRAY FOAM AND NON-FIRE STOPPING MATERIALS - FIRE RATED CAULK WITH MINERAL WOOL BACK-UP, INTUMESCENT COLLARS OR SEAL BAGS FILLED WITH INTUMESCENT MATERIALS ARE REQUIRED TO BE USED TO SEAL ALL PENETRATION HOLES. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS.

  • Open

    CN021042 — GARAGE TO RESIDENTIAL-4HR SEP

    BUILDING SHARED THE SAME GARAGE AT BASEMENT WITH TOWNHOUSES. PROVIDE VESTIBULES WITH TWO CLASS A DOORS TO GARAGE. PLANS AND PERMIT REQUIRED TO INSTALL VESTIBULES, WITH FIRE RATED DOORS - SUBJECT TO FIELD INSPECTION.

  • Open

    CN015062 — OBSTRUCTIONS IN EXIT WAY

    18 TOWNHOUSE BUILDINGS SHARED THE SAME GARAGE WITH 5201 S./ BUILDING AT BASEMENT LEVEL: AUTOMATIC VERTICAL ROLLER SHUTTER DOOR AND A CLASS A DOOR INSTALLED ON BOTH SIDES OF FIRE WALL BETWEEN GARAGE AND DWELLING UNIT. FIRE SHUTTER WILL MAKE IT DIFFICULT FOR THE TENANT TO ESCAPE IN EVENT OF FIRE HAZARD FROM THE UNITS. MOST UNITS, INCLUDING 5D, 6D, 6E, 7D, 8E, 9D, 9E, 10F, 11D, 14E, 16D, 17D, 22E AND 28D - REAR EGRESS OBSTRUCTED BY RACKS, SHELVES AND FURNITURE.

  • Open

    CN197087 — CARB MONOX DETECT IN RESID

    NORTH TOWER: PARTY ROOM KITCHEN - CARBON MONOXIDE DETECTOR - MISSING.

  • Open

    CN197019 — INSTALL SMOKE DETECTORS

    NORTH AND SOUTH TOWERS: 2ND FLOOR STORAGE ROOMS - SMOKE DETECTORS - MISSING.

  • Open

    CN031013 — FIRE EXTNGSHR REQ, RESDNTL

    NORTH AND SOUTH TOWERS: 2ND FLOOR STORAGE ROOMS - FIRE EXTINGUISHERS - MISSING.

  • Open

    CN107025 — INSTALL EXIT SIGN

    NORTH AND SOUTH TOWERS: 2ND FLOOR STORAGE ROOMS - MISSING EXIT AND DIRECTIONAL SIGNS.

  • Open

    EL0036 — COVER OUTLETS AND JBS

    NORTH AND SOUTH TOWERS: 1ST FLOOR SUPPLY STORAGE ROOMS AND PENTHOUSE BOILER ROOM - OPEN JUNCTION BOXES ON WALLS AND CEILINGS.

  • Open

    CN194029 — PROVIDE

    NORTH TOWER / 1ST FLOOR - SUPPLY STORAGE ROOM - MISSING EMERGENCY LIGHT (SEC. 14-8-170)

  • Open

    CN107035 — MAINTAIN EXIT SIGN ILLUMINATED

    PENTHOUSE: BOILER ROOM - EXIT SIGN - BROKEN AND OUT OF SERVICE.

  • Open

    CN194029 — PROVIDE

    SMOKE DETECTORS AND COMMUNICATION SYSTEM INSTALLATION IS IN PROCESS. COMPLETE INSTALLATION OF ONE WAY AND TWO WAY COMMUNICATION SYSTEMS THROUGHOUT THE BUILDING ARE REQUIRED (SEC.13-196-204). COMPLETE INSTALLATION OF WIRED SMOKE DETECTORS THROUGHOUT BUILDING ARE REQUIRED (SEC. 13-196-210).

  • Open

    NC5012 — CLASS B DOOR IN STAIRWELL

    MOST STAIRWAY DOORS, INCLUDING 7A, 7B, 8D, 11D, 17E, 19A, 19B, 19D, 20A, 20B, 20D, 20E, 22A, 22B, 25E, 27D AND 27E - MISSING FIRE RATED LABELS.

  • Open

    CN015072 — BLOCKED FIRE DOOR

    TOWNHOUSE 5123 AND 5139 REAR EXIT DOORS TO GARAGE OBSTRUCTED WITH PVC PIPES FROM FURNACE SYSTEM.

  • Open

    EL0029 — EXPOSED WIRING

    NORTH AND SOUTH TOWERS: PENTHOUSE / BOILER ROOM AND 1ST FLOOR / SUPPLY STORAGE ROOM - OPEN JUNCTION BOXES - EXPOSED WIRES.

  • Open

    NC6042 — SELF-CLOSE DOOR >4 STORY RES.

    UNIT DOORS NOT PROPERLY CLOSING AND LATCHING, SOME WITH WHETHER STRIPPINGS: 3F, 5F, 8F, 12F, 17F, 19D, 22F, 24F AND 27D. MOST UNITS, INCLUDING 22E, 23E, 24D, 26D, 27E AND 28D - REAR EXIT DOORS, MISSING SELF-CLOSING DEVICE. IN ADDTION, VERIFY SELF-CLOSING HARDWARE IS INSTALLED IN ROOMS THAT WERE INACCESSIBLE ON 10/02/14.

  • Open

    CN197039 — RELOCATE SMOKE DETECTOR

    SOUTH STAIRWAY,SMOKE DETECTOR,3 FEET FROM CEILING.

  • Open

    CN079014 — REPAIR/REBUILD GARAGE OR SHED

    GARAGE - (1) ENTIRE GARAGE SEVERE SPALLING CONCRETE, WATER DAMAGE, EXPOSED SEVERELY RUSTED REBAR AND STEEL (2) METAL PANS THROUGHTOUT GARAGE TO PROTECT FROM SPALLING CONCRETE AND WATER SOME PANS HAVE BEGUN TO SEVERELY RUST (3) ALONG A COLUMN SHORING PLACED AROUND COLUMN FOR STRUCTURAL SUPPORT (4) DRAIN PIPING IS SEVERLY RUSTED AND DAMAGED AROUND DRAINS, CONCRETE IS SPALLED (5) WATER DAMAGE THROUGHTOUT CONCRETE WALLS AND CEILINGS, STALACTITES HANGING FROM CEILING, WATER STAINS ALONG WALLS (6) AT VARIOUS LOCATIONS STRUCTURAL CRACKS ALONG CEILING WHERE WATER HAS FILTERED ITSELF THROUGH (7) PLANS AND PERMITS REQUIRED FOR ALL REPAIRS

  • Open

    CN138106 — STOP/REMOVE NUISANCE

    GARAGE - AT ALL LOCATIONS REMOVE ALL PLASTIC GARBAGE CANS AND AT UNIT 5125 ALL FIREWOOD STORED IN PARKING GARAGE IMPROPER STORAGE OF ITEMS IN GARAGE

  • Open

    CN101015 — REPAIR INTERIOR WALLS/CEILING

    STAIRWELL WALL BROKEN PLASTER 27-D,26-D STAIRWELL PEELING PAINT ON CEILING.

  • Open

    CN197039 — RELOCATE SMOKE DETECTOR

    STAIRWELL NO SMOKE DETECTOR

  • Open

    CN196029 — POST OWNER/MANAGERS NAME/#

    BLDG.-MISSING MANAGEMENT SIGN.

About these City violation records

From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”

↑ Back to renter reviews

311 complaints (24 months)

  • other

    No Building Permit and Construction Violation

Timeline

  1. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  2. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  3. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  4. 311 other — No Building Permit and Construction Violation
  5. Open City violation record — EL0019 DEFECTIVE FIXTURES
  6. Open City violation record — CN197087 CARB MONOX DETECT IN RESID
  7. Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
  8. Open City violation record — CN190029 ARRANGE FOR REINSPECTION REGAR
  9. Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
  10. Open City violation record — CN073014 REPAIR EXTERIOR DOOR
  11. Open City violation record — PL154027 SUPPLY HOT WTR MIN TEMP 120DEG
  12. Open City violation record — CN106015 REPAIR INTERIOR STAIR SYSTEM
  13. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  14. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  15. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  16. Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
  17. Open City violation record — NC5042 SELF-CLOSE CLASS B FIRE DOOR
  18. Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
  19. Open City violation record — NC6012 1HR PUB.CORRIDOR IN MULT. D.U.
  20. Open City violation record — CN197019 INSTALL SMOKE DETECTORS
  21. Open City violation record — PL159017 REPLACE DEFECTIVE PLBG FIXTURE
  22. Open City violation record — CN102015 INT WALL/CEILING PEELING PAINT
  23. Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
  24. Open City violation record — CN101015 REPAIR INTERIOR WALLS/CEILING
  25. Open City violation record — CN075014 GRADE AND DRAIN LOT
  26. Open City violation record — CN102015 INT WALL/CEILING PEELING PAINT
  27. Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
  28. Open City violation record — NC5042 SELF-CLOSE CLASS B FIRE DOOR
  29. Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
  30. Open City violation record — NC6012 1HR PUB.CORRIDOR IN MULT. D.U.
  31. Open City violation record — CN075014 GRADE AND DRAIN LOT
  32. Open City violation record — CN196029 POST OWNER/MANAGERS NAME/#
  33. Open City violation record — CN194029 PROVIDE
  34. Open City violation record — CN194029 PROVIDE
  35. Open City violation record — NC6042 SELF-CLOSE DOOR >4 STORY RES.
  36. Open City violation record — EL0029 EXPOSED WIRING
  37. Open City violation record — CN015072 BLOCKED FIRE DOOR
  38. Open City violation record — NC5012 CLASS B DOOR IN STAIRWELL
  39. Open City violation record — CN194029 PROVIDE
  40. Open City violation record — CN107035 MAINTAIN EXIT SIGN ILLUMINATED

Recently closed / other violations (sample)

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    CN101015 REPAIR INTERIOR WALLS/CEILING

  • Closed / other

    PL159017 REPLACE DEFECTIVE PLBG FIXTURE

  • Closed / other

    CN197019 INSTALL SMOKE DETECTORS

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

  • Closed / other

    EV1110 MAINTAIN OR REPAIR ELECT ELEVA

Around 5201 S Cornell Ave

Nearby buildings with open City violation records

Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.

How the winter score is calculated
  1. Start at 100 (better = higher).
  2. Minus up to 40 for open heat/boiler-related building violations (12 pts each).
  3. Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
  4. Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
  5. Minus up to 15 for recent 311 building complaints (2 pts each).
  6. Extra −10 if 3+ open heat-related violations.
  7. Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
  8. Public records only — not an inspection, appraisal, or legal advice.

Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 6:49 AM CT.

ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.

“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.