All open City violation records (59)
3 of 59 open City violation records are from the last 24 months (since November 2024), shown newest first. 56 older ones are collapsed below — still open, still counted.
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
MAKE PROPER REPAIRS TO FIRE SERVICE OPERATION ON ALL ELEVATORS
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
REPLACE ROUGING CABLES ON ELEVATOR 2S.
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
DIAGRAMMATIC REPRESENTATION SHALL BE DISPLAYED AT LOBBY PANEL
Show 56 older open City violation records (before November 2024)
- Open
CN190029 — ARRANGE FOR REINSPECTION REGAR
5201 S. / APARTMENT # 15B - NO ENTRY, UNVERIFIED CONDITIONS AND DETECTORS; UNABLE TO VERIFY COMPLAINT OF APARTMENT INFESTED WITH FLIES, DUE TO TENANT BEING A HOARDER; BAD STENCH; CREATING A RODENT PROBLEM.
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
LAUNDRY ROOM / SMOKE DETECTOR - OUT OF SERVICE AT TIME OF INSPECTION.
- Open
CN197087 — CARB MONOX DETECT IN RESID
LAUNDRY ROOM / CARBON MONOXIDE DETECTOR - OUT OF SERVICE AT TIME OF INSPECTION.
- Open
EL0019 — DEFECTIVE FIXTURES
MULTIPLE LOCATIONS / EXIT SIGNS - NOT ILLUMINATED AT TIME OF INSPECTION.
- Open
CN106015 — REPAIR INTERIOR STAIR SYSTEM
28 FL / STAIRS LEADING TO BOILER ROOM / HANDRAIL - LOOSE AT TOP CONNECTION.
- Open
PL154027 — SUPPLY HOT WTR MIN TEMP 120DEG
BATHROOM AT GRADE AND UNIT 7B / HOT WATER SUPPLIED AT ONLY 100F AT 1:00 PM.
- Open
CN073014 — REPAIR EXTERIOR DOOR
EAST EXIT DOOR AT GROUND FLOOR NEAR BATHROOMS / DOOR IS DRAFTY WITH AIR SEEPAGE.
- Open
CN190019 — ARRANGE PREMISE INSPECTION
INTERIOR OF MOST APTS. - NO RESPONSE, UNVERIIFED DETECTORS AND CONDITIONS.
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
INSTALL BRAILLE PLATES
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
PROVIDE FASCIA EXTENSIONS AS NEEDED TO REMOVE HAZARDS ABOVE HEADERS
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
PROVIDE CLIMATE CONTROL IN MACHINE ROOM
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
LABEL CONTROLLER AND MACHINE
- Open
CN196029 — POST OWNER/MANAGERS NAME/#
BUILDING - NO OWNER'S I.D. SIGN POSTED .
- Open
CN075014 — GRADE AND DRAIN LOT
FRONT DRIVEWAY WORN AND WEATHERED PAVEMENT COATING .
- Open
NC6012 — 1HR PUB.CORRIDOR IN MULT. D.U.
FIRST FLOOR MANAGEMENT OFFICE DOOR BEING HELD OPEN WITHOUT AUTOMATIC RELEASE OR FAILSAFE DEVICE .
- Open
CN101025 — INT WALL/CEILING CHIP PLASTER
26TH FLOOR NORTH HALLWAY - TRASH ROOM , WALLS AND CEILING FLAKING PAINT .
- Open
NC5042 — SELF-CLOSE CLASS B FIRE DOOR
26TH FLOOR NORTH HALLWAY - TRASH ROOM , TRASH CHUTE DOOR NOT AUTO CLOSING AND LATCHING .
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
26TH FLOOR NORTH ELEVATOR HALLWAY - SMOKE DETECTOR OUT OF SERVICE AT TIME OF INSPECTION .
- Open
CN102015 — INT WALL/CEILING PEELING PAINT
FIRST FLOOR MANAGEMENT OFFICE CEILING WATER DAMAGED AND FLAKING .
- Open
CN075014 — GRADE AND DRAIN LOT
FRONT DRIVEWAY WORN AND WEATHERED PAVEMENT COATING .
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
APARTMENT #26B - HALLWAY OUTSIDE BATHROOM , NORTH WALL DRYWALL REPAIRS FROM PIPE REPLACEMENT NOT COMPLETED TO FINISH PAINT . KITCHEN CEILING WATER DAMAGED AT EAST , WALLS PEELING WALLPAPER AT SEAMS . KITCHEN SINK BASE REAR WALL DRYWALL REPAIRS NOT COMPLETED .
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
26TH FLOOR NORTH ELEVATOR HALLWAY - SMOKE DETECTOR OUT OF SERVICE AT TIME OF INSPECTION .
- Open
CN102015 — INT WALL/CEILING PEELING PAINT
FIRST FLOOR MANAGEMENT OFFICE CEILING WATER DAMAGED AND FLAKING .
- Open
PL159017 — REPLACE DEFECTIVE PLBG FIXTURE
APARTMENT #26B - KITCHEN SINK BASE CABINET MISSING FLOOR IN CABINET .
- Open
CN197019 — INSTALL SMOKE DETECTORS
APARTMENT #26B - SMOKE DETECTOR OUT OF SERVICE AND EXPIRED AT TIME OF INSPECTION .
- Open
NC6012 — 1HR PUB.CORRIDOR IN MULT. D.U.
FIRST FLOOR MANAGEMENT OFFICE DOOR BEING HELD OPEN WITHOUT AUTOMATIC RELEASE OR FAILSAFE DEVICE .
- Open
CN101025 — INT WALL/CEILING CHIP PLASTER
26TH FLOOR NORTH HALLWAY - TRASH ROOM , WALLS AND CEILING FLAKING PAINT .
- Open
NC5042 — SELF-CLOSE CLASS B FIRE DOOR
26TH FLOOR NORTH HALLWAY - TRASH ROOM , TRASH CHUTE DOOR NOT AUTO CLOSING AND LATCHING .
- Open
CN194029 — PROVIDE
COMPLETE CITY OF CHICAGO MACHINE ROOM FOR CHILLERS.
- Open
CN194029 — PROVIDE
COMPLETE CITY OF CHICAGO MACHINE ROOM FOR PENTHOUSE CHILLER ROOM. REFRIGERANT SENSORS,MONITOR, AUDIBLE / VISIBLE ALARMS INSIDE AND OUTSIDE ROOM,SCBA OUTSIDE ROOM, REFRIGERANT EXHAUST FAN DUCTED 12" ABOVE FINISHED FLOOR, EMERGENCY SWITCH LOCATED OUSIDE OF ROOM TO ACTIVATE REFRIGERANT EXHAUST FAN AND SIGNAGE LOCATED ON MAIN ENTRY TO ROOM TO READ - HIGH PRESSURE REFRIGERANT -DANGER- IF LIGHT OR ALARM ON . DO NOT ENTER. AUTHORIZED PERSONNEL ONLY
- Open
CN190019 — ARRANGE PREMISE INSPECTION
MOST UNIT DOORS, INCLUDING 3A, 3D, 3E, 4F, 5E, 6B, 7A, 7F, 7E, 8A, 8B, 9B, 9C, 9F, 10D, 11A, 11B, 11C, 11F, 11E, 12D, 14F, 14D,15A, 15B, 15E, 16A, 17B, 17E, 18A, 18E, 18F, 19C, 19F, 20A, 20C, 20D, 20F, 21A, 21B, 21D, 21F, 21E, 22D, 23A, 23C, 23F, 24F, 24E, 25C, 25D, 25E, 26D, 26E, 27A, 27B, 27C, 28C AND TOWNHOUSE 5115, 5117, 5119, 5125, 5127, 5131, 5145 AND 5147 REAR DOORS TO "SHARED GARAGE" WITH 5201 S. / BUILDING: NO RESPONSE - UNABLE TO VERIFY FIRE DOOR RATINGS, SELF-CLOSING AND LATCHING CONDITIONS.
- Open
EL0019 — DEFECTIVE FIXTURES
INTERIOR STAIRWAYS: LLA, 2B, 3D, 5D, 8B, 24D AND 24E - EMERGENCY LIGHTS - BROKEN AND OUT OF SERVICE.
- Open
CN073054 — REPAIR EXTERIOR DOOR, RESET
SOUTH TOWER PENTHOUSE - BOILER ROOM EXTERIOR FIRE DOOR TO ROOF - RUBBING ON SILL, WITH GAP AT TOP.
- Open
NC5042 — SELF-CLOSE CLASS B FIRE DOOR
SOUTH ELEVATOR MACHINE ROOM LOCATED AT MEZZANINE FLOOR OPEN TO BOILER ROOM; SALT / LAWN MOWER / BLOWER STORAGE ROOM, FURNITURE ROOM AND SUPPLY ROOMS - DOORS AND FRAMES MISSING CLASS B LABELS. PENTHOUSE BOILER ROOM - FLOOR HATCH HOLE TO 28TH FLOOR HAS DETACHED NON FIRE RATED WOODEN DOOR; NORTH ELEVATOR MACHINE ROOM - PLYWOOD HOLLOW DOOR - CLASS B DOORS REQUIRED.
- Heat-related
CN043023 — 2 HOUR BOILER ENCLOSURE
NORTH TOWER PENTHOUSE - SECTIONS OF DRYWALL MISSING NEAR THE AIR VENT SHAFT. SOUTH TOWER BOILER ROOM WITH TWO LARGE OPENINGS TO A LARGE HALLWAY, TRASH ROOM AND PUMP ROOM AT LOWER LEVEL OPENING THROUGH CORRIDOR ARE MISSING CLASS B DOORS. PERMIT REQUIRED TO INSTALL FIRE RATED DOORS.
- Open
CN044013 — PIPE OPENING W/NONCOMBUST MATL
SCISSOR STAIRWELLS: MOST LANDINGS, INCLUDING 17A, 27D, 26D AND GAPS FROM 2ND THRU 3RD FLOOR STAIR FLIGHT, NORTH TOWER / 1ST FLOOR SUPPLY STORAGE ROOM, PENTHOUSE / NORTH BOILER ROOM 24"X30" AIR VENT SHAFT, ELEVATOR MACHINE ROOMS AND ELECTRIC METER ROOMS AT 7TH AND 27TH FLOORS - OPEN HOLES ON WALLS, FLOORS AND CEILINGS BY PIPING, CABLES, CONDUITS AND VENT SHAFTS. SOME OF THE PIPE AND CABLE PENETRATION HOLES SEALED WITH CEMENT, SPRAY FOAM AND NON-FIRE STOPPING MATERIALS - FIRE RATED CAULK WITH MINERAL WOOL BACK-UP, INTUMESCENT COLLARS OR SEAL BAGS FILLED WITH INTUMESCENT MATERIALS ARE REQUIRED TO BE USED TO SEAL ALL PENETRATION HOLES. SUBMIT DOCUMENTATION THAT FIRE STOPPING WAS INSTALLED TO MEET RECOGNIZED AGENCY TEST STANDARDS.
- Open
CN021042 — GARAGE TO RESIDENTIAL-4HR SEP
BUILDING SHARED THE SAME GARAGE AT BASEMENT WITH TOWNHOUSES. PROVIDE VESTIBULES WITH TWO CLASS A DOORS TO GARAGE. PLANS AND PERMIT REQUIRED TO INSTALL VESTIBULES, WITH FIRE RATED DOORS - SUBJECT TO FIELD INSPECTION.
- Open
CN015062 — OBSTRUCTIONS IN EXIT WAY
18 TOWNHOUSE BUILDINGS SHARED THE SAME GARAGE WITH 5201 S./ BUILDING AT BASEMENT LEVEL: AUTOMATIC VERTICAL ROLLER SHUTTER DOOR AND A CLASS A DOOR INSTALLED ON BOTH SIDES OF FIRE WALL BETWEEN GARAGE AND DWELLING UNIT. FIRE SHUTTER WILL MAKE IT DIFFICULT FOR THE TENANT TO ESCAPE IN EVENT OF FIRE HAZARD FROM THE UNITS. MOST UNITS, INCLUDING 5D, 6D, 6E, 7D, 8E, 9D, 9E, 10F, 11D, 14E, 16D, 17D, 22E AND 28D - REAR EGRESS OBSTRUCTED BY RACKS, SHELVES AND FURNITURE.
- Open
CN197087 — CARB MONOX DETECT IN RESID
NORTH TOWER: PARTY ROOM KITCHEN - CARBON MONOXIDE DETECTOR - MISSING.
- Open
CN197019 — INSTALL SMOKE DETECTORS
NORTH AND SOUTH TOWERS: 2ND FLOOR STORAGE ROOMS - SMOKE DETECTORS - MISSING.
- Open
CN031013 — FIRE EXTNGSHR REQ, RESDNTL
NORTH AND SOUTH TOWERS: 2ND FLOOR STORAGE ROOMS - FIRE EXTINGUISHERS - MISSING.
- Open
CN107025 — INSTALL EXIT SIGN
NORTH AND SOUTH TOWERS: 2ND FLOOR STORAGE ROOMS - MISSING EXIT AND DIRECTIONAL SIGNS.
- Open
EL0036 — COVER OUTLETS AND JBS
NORTH AND SOUTH TOWERS: 1ST FLOOR SUPPLY STORAGE ROOMS AND PENTHOUSE BOILER ROOM - OPEN JUNCTION BOXES ON WALLS AND CEILINGS.
- Open
CN194029 — PROVIDE
NORTH TOWER / 1ST FLOOR - SUPPLY STORAGE ROOM - MISSING EMERGENCY LIGHT (SEC. 14-8-170)
- Open
CN107035 — MAINTAIN EXIT SIGN ILLUMINATED
PENTHOUSE: BOILER ROOM - EXIT SIGN - BROKEN AND OUT OF SERVICE.
- Open
CN194029 — PROVIDE
SMOKE DETECTORS AND COMMUNICATION SYSTEM INSTALLATION IS IN PROCESS. COMPLETE INSTALLATION OF ONE WAY AND TWO WAY COMMUNICATION SYSTEMS THROUGHOUT THE BUILDING ARE REQUIRED (SEC.13-196-204). COMPLETE INSTALLATION OF WIRED SMOKE DETECTORS THROUGHOUT BUILDING ARE REQUIRED (SEC. 13-196-210).
- Open
NC5012 — CLASS B DOOR IN STAIRWELL
MOST STAIRWAY DOORS, INCLUDING 7A, 7B, 8D, 11D, 17E, 19A, 19B, 19D, 20A, 20B, 20D, 20E, 22A, 22B, 25E, 27D AND 27E - MISSING FIRE RATED LABELS.
- Open
CN015072 — BLOCKED FIRE DOOR
TOWNHOUSE 5123 AND 5139 REAR EXIT DOORS TO GARAGE OBSTRUCTED WITH PVC PIPES FROM FURNACE SYSTEM.
- Open
EL0029 — EXPOSED WIRING
NORTH AND SOUTH TOWERS: PENTHOUSE / BOILER ROOM AND 1ST FLOOR / SUPPLY STORAGE ROOM - OPEN JUNCTION BOXES - EXPOSED WIRES.
- Open
NC6042 — SELF-CLOSE DOOR >4 STORY RES.
UNIT DOORS NOT PROPERLY CLOSING AND LATCHING, SOME WITH WHETHER STRIPPINGS: 3F, 5F, 8F, 12F, 17F, 19D, 22F, 24F AND 27D. MOST UNITS, INCLUDING 22E, 23E, 24D, 26D, 27E AND 28D - REAR EXIT DOORS, MISSING SELF-CLOSING DEVICE. IN ADDTION, VERIFY SELF-CLOSING HARDWARE IS INSTALLED IN ROOMS THAT WERE INACCESSIBLE ON 10/02/14.
- Open
CN197039 — RELOCATE SMOKE DETECTOR
SOUTH STAIRWAY,SMOKE DETECTOR,3 FEET FROM CEILING.
- Open
CN079014 — REPAIR/REBUILD GARAGE OR SHED
GARAGE - (1) ENTIRE GARAGE SEVERE SPALLING CONCRETE, WATER DAMAGE, EXPOSED SEVERELY RUSTED REBAR AND STEEL (2) METAL PANS THROUGHTOUT GARAGE TO PROTECT FROM SPALLING CONCRETE AND WATER SOME PANS HAVE BEGUN TO SEVERELY RUST (3) ALONG A COLUMN SHORING PLACED AROUND COLUMN FOR STRUCTURAL SUPPORT (4) DRAIN PIPING IS SEVERLY RUSTED AND DAMAGED AROUND DRAINS, CONCRETE IS SPALLED (5) WATER DAMAGE THROUGHTOUT CONCRETE WALLS AND CEILINGS, STALACTITES HANGING FROM CEILING, WATER STAINS ALONG WALLS (6) AT VARIOUS LOCATIONS STRUCTURAL CRACKS ALONG CEILING WHERE WATER HAS FILTERED ITSELF THROUGH (7) PLANS AND PERMITS REQUIRED FOR ALL REPAIRS
- Open
CN138106 — STOP/REMOVE NUISANCE
GARAGE - AT ALL LOCATIONS REMOVE ALL PLASTIC GARBAGE CANS AND AT UNIT 5125 ALL FIREWOOD STORED IN PARKING GARAGE IMPROPER STORAGE OF ITEMS IN GARAGE
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
STAIRWELL WALL BROKEN PLASTER 27-D,26-D STAIRWELL PEELING PAINT ON CEILING.
- Open
CN197039 — RELOCATE SMOKE DETECTOR
STAIRWELL NO SMOKE DETECTOR
- Open
CN196029 — POST OWNER/MANAGERS NAME/#
BLDG.-MISSING MANAGEMENT SIGN.
About these City violation records
From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”
311 complaints (24 months)
- other
No Building Permit and Construction Violation
Timeline
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- 311 other — No Building Permit and Construction Violation
- Open City violation record — EL0019 DEFECTIVE FIXTURES
- Open City violation record — CN197087 CARB MONOX DETECT IN RESID
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — CN190029 ARRANGE FOR REINSPECTION REGAR
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — CN073014 REPAIR EXTERIOR DOOR
- Open City violation record — PL154027 SUPPLY HOT WTR MIN TEMP 120DEG
- Open City violation record — CN106015 REPAIR INTERIOR STAIR SYSTEM
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — NC5042 SELF-CLOSE CLASS B FIRE DOOR
- Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
- Open City violation record — NC6012 1HR PUB.CORRIDOR IN MULT. D.U.
- Open City violation record — CN197019 INSTALL SMOKE DETECTORS
- Open City violation record — PL159017 REPLACE DEFECTIVE PLBG FIXTURE
- Open City violation record — CN102015 INT WALL/CEILING PEELING PAINT
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — CN101015 REPAIR INTERIOR WALLS/CEILING
- Open City violation record — CN075014 GRADE AND DRAIN LOT
- Open City violation record — CN102015 INT WALL/CEILING PEELING PAINT
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — NC5042 SELF-CLOSE CLASS B FIRE DOOR
- Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
- Open City violation record — NC6012 1HR PUB.CORRIDOR IN MULT. D.U.
- Open City violation record — CN075014 GRADE AND DRAIN LOT
- Open City violation record — CN196029 POST OWNER/MANAGERS NAME/#
- Open City violation record — CN194029 PROVIDE
- Open City violation record — CN194029 PROVIDE
- Open City violation record — NC6042 SELF-CLOSE DOOR >4 STORY RES.
- Open City violation record — EL0029 EXPOSED WIRING
- Open City violation record — CN015072 BLOCKED FIRE DOOR
- Open City violation record — NC5012 CLASS B DOOR IN STAIRWELL
- Open City violation record — CN194029 PROVIDE
- Open City violation record — CN107035 MAINTAIN EXIT SIGN ILLUMINATED
Recently closed / other violations (sample)
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
CN101015 REPAIR INTERIOR WALLS/CEILING
- Closed / other
PL159017 REPLACE DEFECTIVE PLBG FIXTURE
- Closed / other
CN197019 INSTALL SMOKE DETECTORS
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
Around 5201 S Cornell Ave
- Hyde Park building violations and 311 complaints
- UChicago off-campus housing: Hyde Park renter guide
- No heat in your Chicago apartment? The heat ordinance and what to do
Nearby buildings with open City violation records
Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.
How the winter score is calculated
- Start at 100 (better = higher).
- Minus up to 40 for open heat/boiler-related building violations (12 pts each).
- Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
- Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
- Minus up to 15 for recent 311 building complaints (2 pts each).
- Extra −10 if 3+ open heat-related violations.
- Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
- Public records only — not an inspection, appraisal, or legal advice.
Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 6:49 AM CT.
ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.
“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.