1734 W Greenleaf Ave

Winter habitability score Many open City violation records and/or complaint activity

Download a PDF of this report

Renter reviews

Firsthand and anonymous. Renter opinions are separate from the city records below.

No renter reviews here yet. If you’ve lived at 1734 W Greenleaf Ave, yours could be the first.

A Chicago three-flat

Do you live here?

One tap helps other renters. The full building record stays right below.

Sure, I’ll share
How’s it been living here? Required

Tap a star — 1 is rough, 5 is great.

Add more detail (optional — heat, pests, repairs, noise, management)

Tap 1 to 5 for any you want. 1 is rough, 5 is great. Skip the rest.

Heat Warm enough when it counts?
Pests Have pests been a problem?
Maintenance responsiveness When something broke, how fast did it get fixed?
Noise How noisy was it, day to day?
Management How they treated you and answered you
Would you rent here again?

Your own experience only — no fake or paid reviews. Shown anonymously after you confirm and a person approves it. Review policy · Terms

39Open City violation records
2Open heat-related City records
0311 rodent (24 mo)
0311 building (24 mo)

What rat complaints mean →

All open City violation records (39)

No open City violation records dated in the last 24 months (since November 2024). The newest open one is from February 15, 2023. All 39 are collapsed below — still open, still counted.

Show 39 older open City violation records (before November 2024)
  • Open

    EL1884 — SEE INSPECTOR COMMENTS

    1740 2ND FLOOR PROVIDE PERMIT TO CORRECT VIOLATIONS (14A-4-404.6)

  • Open

    CN190019 — ARRANGE PREMISE INSPECTION

    ALLOW FULL INTERIOR INSPECTION AT PROPERTY, ENTRY ONLY 2 EAST AT TIME OF INSPECTION (14A-1-104.7)

  • Open

    CN065014 — REPAIR LINTELS

    RUSTED LINTELS AT SOUTH ELEVATIONS 2ND FLOOR (14X-3-303.1.1)

  • Open

    CN031033 — FIRE EXTNGSHR REQ, NONRESDNTL

    MISSING FIRE EXTINGUISHERS UNIT 2 EAST COMMERCIAL SPACE (14X5-504.5)

  • Open

    CN197087 — CARB MONOX DETECT IN RESID

    MISSING CARBON MONOXIDE DETECTORS THROUGHOUT UNIT 2 EAST COMMERCIAL SPACE (14X-5-504.9)

  • Heat-related

    CN010012 — 1-HR HEATING PLANT ENCLOSURE

    FURNACE ROOM LOCATED WITHIN UNIT 2 EAST MISSING SECTIONS OF FIRE SEPARATION AT CEILINGS 1 HOUR ENCLOSURE REQUIRED (14B-5-509)

  • Heat-related

    CN011012 — HEATING PLANT/BOILER ROOM DOOR

    90 MINUTE DOOR REQUIRED FOR FURNACE ROOM ENCLOSURE (14B-7-716)

  • Open

    CN106015 — REPAIR INTERIOR STAIR SYSTEM

    STAIRS LEADING TO 2ND FLOOR TRACTION MATS CAUSING TRIP HAZARDS (14X-3-304.4)

  • Open

    CN070014 — REPAIR EXTERIOR STAIR

    REAR OF PROPERTY 2 STORY IRON PORCH STRUCTURE NOT FASTENED TO GROUND LEVEL LANDING (14X-3-303.1.1)

  • Open

    CN061014 — REPAIR EXTERIOR WALL

    REAR OF PROPERTY SPALLING BRICK AND MISSING MORTAR (14X-3-303.1.1)

  • Open

    PL234002 — SOIL/WASTE,VENT PIPE MATRL

    UNAPPROVED PVC PIPING AT BATHROOM LAVATORIES AND LAUNDRY TUB WASTE AT UNIT 2E

  • Open

    PL163027 — PROVIDE OPEN FRONT TOILET SEAT

    UNAPPROVED ROUND BOWL TOILETS WITH CLOSED FRONT SEATS AT MENS AND WOMEN BATHROOM UNIT 2E

  • Open

    PL234018 — INSTALL VENT PIPE FOR TRAP

    BATHROOM LAVATORIES AND LAUNDRY TUB FIXTURE TRAPS ARE NOT VENTED IN UNIT 2E

  • Open

    PL194039 — REMOVE

    BATHROOM LAVATORIES MISSING MIXING VALVES A UNIT 2E (18-29-607X

  • Open

    PL237048 — OPEN

    BATHROOMS IN UNIT 2E MISSING FLOOR DRAINS (18-29-412-4.3)

  • Open

    PL159017 — REPLACE DEFECTIVE PLBG FIXTURE

    TOILET AT MENS BATHROOM IN UNIT 2E IS ONLY 10" FROM SIDE WALL NOT MEETING MINIMUM REQUIRED OF 15" CLEARANCE

  • Open

    PL159017 — REPLACE DEFECTIVE PLBG FIXTURE

    LAUNDRY TUB AT UNIT 2E IS ONLY SUPPLIED WITH COLD WATER FROM A BOILER DRAIN WITH NO FACET ATTACHED

  • Open

    PL237014 — PRV BALLCOCK,VB,OR AIR GAP

    LAUNDRY TUB WATER SUPPLY CONSISTS OF A BOILER DRAIN DISCHARGING BELOW FLOOD LEVEL RIM WITHOUT ANY MEANS OF BACKFLOW PREVENTION

  • Open

    PL232011 — OBTAIN PERMIT FOR PLUMBING

    OBTAIN PERMIT BEFORE CONSTRUCTING ALERTING OF USING PLUMBING SYSTEM

  • Open

    PL239010 — ENGAG LIC & BOND PLMBNG CNTRC

    ENGAGE LICENSED AND BONDED PLUMBING CONTRACTOR TO INSTALL PLUMBING

  • Open

    EL1866 — UNAPPROVED CORDS

    1740 2ND FLOOR EXCESSIVE UNAPPROVED EXTENSION CORDS THROUGHOUT SPACE REMOVE WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1810 — TENANT ACCESS TO SERVICE

    1740 2ND FLOOR TENANT DOES NOT HAVE ACCESS TO PANEL DANGEROUS AND HAZARDOUS

  • Open

    EL1816 — ADD RECEPTACLES

    1740 2ND FLOOR ADD RECEPTACLE OUTLETS WHERE REQUIRED TO AVOID EXTENSION CORD USAGE DANGEROUS AND HAZARDOUS

  • Open

    EL1823 — INSTALL COVERS

    1740 2ND FLOOR OPEN ELECTRICAL BOX AT MECHANICAL ROOM CEILING CLOSE WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1880 — DETERIORATED CONDUCTORS

    1740 2ND FLOOR DETERIORATED CLOTH WIRING VISIBLE AT OPEN BOX MECHANICAL ROOM CEILING REPLACE WHERE REQUORED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1826 — SYSTEM II

    1740 2ND FLOOR EXISTING EMERGENCY LIGHTING SYSTEM NOT APPROVED NOT SUFFICIENT INSTALL REQUIRED SYSTEM WHERE REQUIRED PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1819 — DEFECTIVE FIXTURES

    1740 2ND FLOOR DAMAGED LIGHT FIXTURE MECHANICAL ROOM CEILING REPAIR/REPLACE WHERE REQUIRED THROUGHOUT PREMISES

  • Open

    EL1824 — INSTALL ILLUMINATION

    1740 2NED FLOOR INSUFFICIENT ILLUMINATION THROUGHOUT SPACE INSTALL WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1833 — SECURE RACEWAY

    1740 2ND FLOOR UNSUPPORTED RACEWAY MECHANICAL ROOM SECURE WHERE REQUIRED

  • Open

    EL1801 — DEFECTIVE SERVICE

    7047-53 MULTIPLE ELECTRICAL SERVICES AT EAST EXTERIOR ARE IN DETERIORATED STATE MIDDLE ELECTRICAL SERVICE HAS DETERIORATED RISER, DETERIORATED SUPPORTS DETERIORATED CABLES VISIBLE AT HEAD DETERIORATED INACCESSIBLE OPEN MOGUL SOUTH ELECTRICAL SERVICE HAS DETERIORATED RISER,DETERIORATED SUPPORTS, DETERIORATED CABLE ENSURE ALL SERVICES IN APPROVED CONDITION DANGEROUS AND HAZARDOUS

  • Open

    EL1824 — INSTALL ILLUMINATION

    7047-53 INSUFFICIENT ILLUMINATION 1740 COMMON INTERIOR STAIRWELL 1740 FRONT ENTRY AREA, ALL REAR EXTERIOR ENTRIES ALL REAR EXTERIOR STAIRS INSTALL ILLUMINATION WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1822 — EXPOSED WIRING FIXTURES

    7047-53 PENDANT LIGHT FIXTURE AT 1740 COMMON INTERIOR STAIRWELL HAS DAMAGED OPEN AIR SPLICED WIRING REMOVE OPEN WIRING AT LIGHT FIXTURES WHERE REQUIRED THROUGHOUT PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1819 — DEFECTIVE FIXTURES

    7047-53 DAMAGED LIGHT FIXTURE AT 1740 FRONT ENTRY REPLACE LIGHT FIXTURES WHERE REQUIRED THROUGHOUT

  • Open

    EL1816 — ADD RECEPTACLES

    7047-53 ADD RECEPTACLE OUTLETS TO ELIMINATE THE USE OF EXTENSION CORDS AT 1740 FRONT INTERIOR UNAPPROVED SIGN CORD CONNECTION TO LIGHT FIXTURE AT 1740 FRONT ENTRY AND WHERE REQUIRED THROUGHOUT ENTIRE PREMISES DANGEROUS AND HAZARDOUS

  • Open

    EL1884 — SEE INSPECTOR COMMENTS

    7047-53 ALL EXTERIOR LIGHT FIXTURES, BOXES,FITTINGS, RACEWAYS MUST BE SUITABLE FOR WET LOCATIONS (14E-1-110.3)

  • Open

    EL1866 — UNAPPROVED CORDS

    7047-53 UNAPPROVED EXTENSION CORDS WRAPPED AROUND SIGNS STRUCTURE AT SOUTH WEST EXTERIOR ENTRY REMOVE UNAPPROVED CORDS WHERE REQUIRED DANGEROUS AND HAZARDOUS

  • Open

    EL1848 — CORD WIRED EQUIPMENT

    7047-53 DAMAGED APPROVED EQUIPMENT CORD AT REAR WEST EXTERIOR REMOVE WHERE REQUIRED DANGEOUS AND HAZARDOUS

  • Open

    EL1885 — Violation

    7047-53 PROVIDE ACCESS INSPECT ELECTRICAL SERVICE AND DISTRIBUTION EQUIPMENT THROUGHOUT PREMISES (14A-5-505.2)

  • Open

    EL1886 — Violation

    7047-53 OBTAIN PERMIT TO CORRECT VIOLATIONS (14A-4-404.6)

About these City violation records

From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”

↑ Back to renter reviews

311 complaints (24 months)

No matching 311 complaints in the last 24 months.

Timeline

  1. Open City violation record — EL1886
  2. Open City violation record — EL1885
  3. Open City violation record — EL1848 CORD WIRED EQUIPMENT
  4. Open City violation record — EL1866 UNAPPROVED CORDS
  5. Open City violation record — EL1884 SEE INSPECTOR COMMENTS
  6. Open City violation record — EL1816 ADD RECEPTACLES
  7. Open City violation record — EL1819 DEFECTIVE FIXTURES
  8. Open City violation record — EL1822 EXPOSED WIRING FIXTURES
  9. Open City violation record — EL1824 INSTALL ILLUMINATION
  10. Open City violation record — EL1801 DEFECTIVE SERVICE
  11. Open City violation record — EL1833 SECURE RACEWAY
  12. Open City violation record — EL1824 INSTALL ILLUMINATION
  13. Open City violation record — EL1819 DEFECTIVE FIXTURES
  14. Open City violation record — EL1826 SYSTEM II
  15. Open City violation record — EL1880 DETERIORATED CONDUCTORS
  16. Open City violation record — EL1823 INSTALL COVERS
  17. Open City violation record — EL1816 ADD RECEPTACLES
  18. Open City violation record — EL1810 TENANT ACCESS TO SERVICE
  19. Open City violation record — EL1866 UNAPPROVED CORDS
  20. Open City violation record — PL239010 ENGAG LIC & BOND PLMBNG CNTRC
  21. Open City violation record — PL232011 OBTAIN PERMIT FOR PLUMBING
  22. Open City violation record — PL237014 PRV BALLCOCK,VB,OR AIR GAP
  23. Open City violation record — PL159017 REPLACE DEFECTIVE PLBG FIXTURE
  24. Open City violation record — PL159017 REPLACE DEFECTIVE PLBG FIXTURE
  25. Open City violation record — PL237048 OPEN
  26. Open City violation record — PL194039 REMOVE
  27. Open City violation record — PL234018 INSTALL VENT PIPE FOR TRAP
  28. Open City violation record — PL163027 PROVIDE OPEN FRONT TOILET SEAT
  29. Open City violation record — PL234002 SOIL/WASTE,VENT PIPE MATRL
  30. Open City violation record — CN061014 REPAIR EXTERIOR WALL
  31. Open City violation record — CN070014 REPAIR EXTERIOR STAIR
  32. Open City violation record — CN106015 REPAIR INTERIOR STAIR SYSTEM
  33. Open heat-related City violation record — CN011012 HEATING PLANT/BOILER ROOM DOOR
  34. Open heat-related City violation record — CN010012 1-HR HEATING PLANT ENCLOSURE
  35. Open City violation record — CN197087 CARB MONOX DETECT IN RESID
  36. Open City violation record — CN031033 FIRE EXTNGSHR REQ, NONRESDNTL
  37. Open City violation record — CN065014 REPAIR LINTELS
  38. Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
  39. Open City violation record — EL1884 SEE INSPECTOR COMMENTS

Recently closed / other violations (sample)

No recent closed violations in the sample.

Around 1734 W Greenleaf Ave

Nearby buildings with open City violation records

Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.

How the winter score is calculated
  1. Start at 100 (better = higher).
  2. Minus up to 40 for open heat/boiler-related building violations (12 pts each).
  3. Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
  4. Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
  5. Minus up to 15 for recent 311 building complaints (2 pts each).
  6. Extra −10 if 3+ open heat-related violations.
  7. Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
  8. Public records only — not an inspection, appraisal, or legal advice.

Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 12:21 PM CT.

ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.

“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.

Check another address

Help: hello@scoutmybuilding.com