All open City violation records (42)
No open City violation records dated in the last 24 months (since November 2024). The newest open one is from August 27, 2019. All 42 are collapsed below — still open, still counted.
Show 42 older open City violation records (before November 2024)
- Open
CN190029 — ARRANGE FOR REINSPECTION REGAR
INTERIOR OF BUILDING /REFUSED ENTRY. UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO INSPECT INTERIOR STAIRWAY SYSTEMS AND BASEMENT.
- Open
CN198019 — FILE BLDG REGISTRATION
BUILDING NOT REGISTERED FROM 2006 THRU 2012.
- Open
CN190019 — ARRANGE PREMISE INSPECTION
NO RESPONSE/ENTRY AT TIME OF INSPECTION TO VERIFY OCCUPANCY,DETECTORS AND OVERALL CONDITION FOR 2012 ANNUAL INSPECTION.
- Open
CN065014 — REPAIR LINTELS
NORTH ELEVATION WITH RUSTING AND SAGGING LINTELS OVER 1615 AND 1625 ENTRIES AT 3RD FLOOR WINDOWS.
- Open
CN061014 — REPAIR EXTERIOR WALL
EAST AND SOUTH ELEVATIONS ABOVE GROUND WITH FRACTURED SKIM COATS, LOOSE MORTAR, SPALLING SECTIONS, ERODED MORTAR. SOUTH ELEVATION TOWARD EAST END WITH AREAS OF ERODED MORTAR AND SPALLING BRICK.
- Open
CN015062 — OBSTRUCTIONS IN EXIT WAY
SOUTH ELEVATION GATE TO STAIR SYSTEM CHAINED AND PAD LOCKED.
- Open
CN062024 — PARAPET
EAST ELEVATION TOWARD NORTH END, AND EAST ELEVATION TOWARD SOUTH END WITH AREAS OF SPALLING BRICK, FRACTURES, LOOSE MORTAR.
- Open
CN065014 — REPAIR LINTELS
NORTH ELEVATION WITH RUSTING AND SAGGING LINTELS OVER 1615 AND 1625 ENTRIES AT 3RD FLOOR WINDOWS.
- Open
CN190019 — ARRANGE PREMISE INSPECTION
NO ENTRY INTERIOR.
- Open
CN193029 — WATCHMAN
ALL KEY LOCKS, DOOR PANES & MAILBOXES VANDALIZED BY CRIMINALS (13-12-140)
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
DEFECTIVE SMOKE DETECTORS
- Open
CN105025 — REPAIR DOOR FRAME, MULLION
BROKEN DOOR FRAME 1619 APT 3E
- Rodent-related
CN136016 — ROACHES
ROACHES INFESTING THE WHOLE BUILDING-1619 3E,3F.1621 APT 2P, 20
- Rodent-related
CN135016 — MICE/RODENTS
MICE IN THE BUILDING-1621 APT 2P, 2O
- Open
CN136026 — INSECTS
INSECTS-BUGS IN 1619 APT 3F, 3E
- Open
CN105015 — REPAIR DOOR, INT.
BROKEN DOOR PANE-REAR DOOR APT 3F
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
CEILING & WALL DAMAGE DUE TO LEAK, APT 3F 1619
- Open
EL0018 — DEFECTIVE OUTLETS
DEFECTIVE WALL OUTLET-BATHROOM 1619 APT 3F + ALL SCOKET IN THE UNIT 3F.
- Open
CN197019 — INSTALL SMOKE DETECTORS
SMOKE DETECTOR MISSING-ALL INTERIOR STAIRWAYS + 1619 APT 3
- Open
PL154027 — SUPPLY HOT WTR MIN TEMP 120DEG
LOW PRESSURE HOT WATER TAP-1619 APT 3E, 3F
- Heat-related
PL155027 — PROVIDE HOT WATER TO FIXTURES
LOW PRESSURE COLD WATER TAP-1619 APT 3E, 3F
- Open
PL163017 — REPLACE DEFECTIVE TOILET SEAT
TOILET SEAT BORKEN & LOOSEN FROM THE FLOOR-BATHROOM 1619 APT 3F
- Open
CN105035 — REPAIR DOOR HARDWARE
BROKEN DOOR LOCKS-BATHROOM & ENTRANCE DOOR 1619 APT 3F
- Open
EL0020 — SUPPORT FIXTURES
LOOSE CEILING FAN-BEDROOM 1619 APT 3F
- Open
CN140016 — DWELLING CLEAN AND SANITARY
THE WHOLE BUILDING INTERIOR HALLWAYS + STAIRWAYS ARE DIRTY AND LITTERED WITH DECAYED FOODS.
- Open
CN138026 — USE SANITARY REFUSE CONTAINERS
REFUSE + GARBAGE ACCUMULATED IN ALL INTERIOR STAIRWAYS + HALLWAYS-1619 STAIRWAY
- Open
CN138056 — DEBRIS, EXCESSIVE
JUNK AND REFUSE ACCUMULATION-ALL INTERIOR HALLWAYS STAIRWAYS, REAR YARDS.
- Open
CN141016 — STOP SMOKE, NOXIOUS ODORS
NOXIOUS ODOR PERMEATING DWELLING UNITS-1621 1ST & 3RD FLOOR UNITS
- Open
CN192019 — NOTIFY DOB, USE OF VACANT LND
MOST BUILDING UNITS VACANT & NOT SECURED-1621-25 1ST TO 3RD FLOORS (13-12-125)
- Open
CN193019 — REPAIR/WRECK DANGER RESID PREM
ALL ENTRANCE DOORS & MAILBOXES VANDALIZED BY THIEVES (18-8-100,12-12-125)
- Open
CN066034 — REPAIR BALCONY
REAR EAST BALCONIES-ROOF BEAMS NOT SECURE TO COLUMNS; ROOF DECK BEAMS WORN OUT
- Open
CN070024 — REPAIR PORCH SYSTEM
1619 SOUTH PORCH SYSTEM-LOOSE & MISSING TREADS & RISERS (1ST TO 2ND FLOOR); GUARD RAILS 42" HIGH; RAILING LOOSEN AND DEFLECTING;LEDGERS & STRINGERS NOT BOLTED
- Open
CN070014 — REPAIR EXTERIOR STAIR
INTERIOR STAIR 1619-21-MISSING LOT OF PICKETS AND COLUMN CAPS. OBTAIN PERMIT TO REPAIR ALL REAR PORCHES AND INTERIOR STAIR SYSTEMS
- Open
EL0001 — DEFECTIVE LIGHTING SERVICE
DETERIORATED CABLES AT SERVICE HEAD
- Open
EL0084 — SEE INSPECTOR COMMENTS
CONDUCTORS AND ELECTRICAL EQUIPMENT SHALL BE SUITABLE FOR THE LOCATION AND TEMPERATURE PROVIDE WEATHERPROOF BOX AND LITE FIXTURE FOR ALL PORCH AREA'S 18-27-110.11
- Open
EL0041 — GROUNDING RECEPTACLES
IN ALL STAIRWAYS AND UNIT 1619 2F
- Open
EL0039 — CORRODED CONDUIT & EQUIP
ALL PORCH LITES AND CONDUIT RUNS
- Open
EL0025 — SYSTEM III
IN ALL STAIRWAYS,CORRIDORS AND COMMON AREA'S OF BUILDING
- Open
EL0022 — EXPOSED WIRING FIXTURES
UNIT 1619 2F KITCHEN LITE
- Open
EL0019 — DEFECTIVE FIXTURES
THRU OUT ALL STAIRWAY AREA'S AND UNIT 1619 2F BATHROOM AND KITCHEN AREA
- Open
EL0016 — ADD RECEPTACLES
TO EASE EXTENSION CORD USE IN KITCHEN AND LIVING,BEDROOM AREA'S OF UNIT 1619 2F
- Open
EL0010 — TENANT ACCESS TO SERVICE
ACCESS TO PANELS AT ALL TIMES ALL TENANTS
About these City violation records
From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”
311 complaints (24 months)
No matching 311 complaints in the last 24 months.
Timeline
- Open City violation record — CN190029 ARRANGE FOR REINSPECTION REGAR
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — CN198019 FILE BLDG REGISTRATION
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — CN065014 REPAIR LINTELS
- Open City violation record — CN062024 PARAPET
- Open City violation record — CN015062 OBSTRUCTIONS IN EXIT WAY
- Open City violation record — CN061014 REPAIR EXTERIOR WALL
- Open City violation record — CN065014 REPAIR LINTELS
- Open City violation record — CN070014 REPAIR EXTERIOR STAIR
- Open City violation record — CN070024 REPAIR PORCH SYSTEM
- Open City violation record — CN066034 REPAIR BALCONY
- Open City violation record — CN193019 REPAIR/WRECK DANGER RESID PREM
- Open City violation record — CN192019 NOTIFY DOB, USE OF VACANT LND
- Open City violation record — CN141016 STOP SMOKE, NOXIOUS ODORS
- Open City violation record — CN138056 DEBRIS, EXCESSIVE
- Open City violation record — CN138026 USE SANITARY REFUSE CONTAINERS
- Open City violation record — CN140016 DWELLING CLEAN AND SANITARY
- Open City violation record — EL0020 SUPPORT FIXTURES
- Open City violation record — CN105035 REPAIR DOOR HARDWARE
- Open City violation record — PL163017 REPLACE DEFECTIVE TOILET SEAT
- Open heat-related City violation record — PL155027 PROVIDE HOT WATER TO FIXTURES
- Open City violation record — PL154027 SUPPLY HOT WTR MIN TEMP 120DEG
- Open City violation record — CN197019 INSTALL SMOKE DETECTORS
- Open City violation record — EL0018 DEFECTIVE OUTLETS
- Open City violation record — CN101015 REPAIR INTERIOR WALLS/CEILING
- Open City violation record — CN105015 REPAIR DOOR, INT.
- Open City violation record — CN136026 INSECTS
- Open City violation record — CN135016 MICE/RODENTS
- Open City violation record — CN136016 ROACHES
- Open City violation record — CN105025 REPAIR DOOR FRAME, MULLION
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — CN193029 WATCHMAN
- Open City violation record — EL0010 TENANT ACCESS TO SERVICE
- Open City violation record — EL0016 ADD RECEPTACLES
- Open City violation record — EL0019 DEFECTIVE FIXTURES
- Open City violation record — EL0022 EXPOSED WIRING FIXTURES
- Open City violation record — EL0025 SYSTEM III
- Open City violation record — EL0039 CORRODED CONDUIT & EQUIP
- Open City violation record — EL0041 GROUNDING RECEPTACLES
Recently closed / other violations (sample)
- Closed / other
CN067014 REPAIR ROOF
- Closed / other
CN138106 STOP/REMOVE NUISANCE
- Closed / other
CN077014 REPAIR FENCE
- Closed / other
CN073024 REPAIR EXTERIOR DOOR FRAME
- Closed / other
CN069014 REPAIR DEFECTIVE FOUNDATION
- Closed / other
CN137026 TIGHT GARBAGE COVERS
- Closed / other
CN068014 REPAIR ROOF STRUCTURE
- Closed / other
CN131016 SCREEN OUTER DOORS, WINDOWS
- Closed / other
NC2022 BLANK-TEXT MUST CITE CODE SECT
- Closed / other
CN196029 POST OWNER/MANAGERS NAME/#
- Closed / other
CN198019 FILE BLDG REGISTRATION
- Closed / other
CN190019 ARRANGE PREMISE INSPECTION
- Closed / other
CN062024 PARAPET
- Closed / other
CN065014 REPAIR LINTELS
- Closed / other
CN015062 OBSTRUCTIONS IN EXIT WAY
- Closed / other
CN061014 REPAIR EXTERIOR WALL
Around 1615 W Columbia Ave
- Rogers Park building violations and 311 complaints
- Loyola Chicago off-campus housing: Rogers Park renter guide
- No heat in your Chicago apartment? The heat ordinance and what to do
Nearby buildings with open City violation records
Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.
How the winter score is calculated
- Start at 100 (better = higher).
- Minus up to 40 for open heat/boiler-related building violations (12 pts each).
- Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
- Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
- Minus up to 15 for recent 311 building complaints (2 pts each).
- Extra −10 if 3+ open heat-related violations.
- Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
- Public records only — not an inspection, appraisal, or legal advice.
Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 12:28 PM CT.
ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.
“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.