All open City violation records (42)
No open City violation records dated in the last 24 months (since November 2024). The newest open one is from February 6, 2014. All 42 are collapsed below — still open, still counted.
Show 42 older open City violation records (before November 2024)
- Open
CN066014 — REPAIR ORIEL WINDOW
EAST ELEVATIONS - MOST WINDOWS, INCLUDING ROOM 11 AND 13 - EXTERIOR ORIEL WINDOW WALL UNFINISHED - EXPOSED TO WEATHER.
- Open
CN103035 — STRUCTURAL MEMBER, PIER BLOCK
2ND FLOOR HALLWAY - FLOOR STRUCTURE BUCKLED AND SWAYING.
- Open
CN103025 — SUBMIT STRUCT. ENG. RPT (INT.)
SUBMIT STRUCTURE ENGINEER'S REPORT ON STABILITY OF 2ND FLOOR HALLWAY FLOOR SYSTEM.
- Open
CN104035 — MAINTAIN WINDOW
ROOM 11 AND 13 - UNFINISHED WINDOW FRAMES - EXPOSURE TO WEATHER.
- Open
NC2071 — WORK NOT ALLOWED
ROOMING UNIT # 16 BUILT ON REAR PORCH DECK. REMOVE ALL PARTITIONS AND FIXTURES (INCLUDING PLUMBING AND ELECTRIC) INSTALLED IN ROOM 16 WITHOUT A PERMIT.
- Open
NC2011 — PLANS & PERMITS REQ - CONTRCTR
ENTIRE BUILDING: OCCUPANCY CHANGED FROM COMMERCIAL / ONE DWELLING UNIT TO SINGLE ROOM OCCUPANY (S.R.O), INCLUDING ADDITIONAL ROOM ON 2ND FLOOR REAR PORCH DECK. SUBMIT PLANS AND OBTAIN PERMIT FOR ALL RELATED WORK TO AUTHORIZE ALTERATIONS TO 1ST AND 2ND FLOOR, OR RESTORE THE BUILDING TO THE ORIGINAL STATE.
- Open
CN197019 — INSTALL SMOKE DETECTORS
ROOM 16 - SMOKE DETECTOR - MISSING.
- Open
CN194029 — PROVIDE
1ST AND 2ND FLOOR - EXIT DOORS - ONLY 32 INCHES WIDE. (SEE SECTION 13-160-220).
- Open
CN015012 — NO KEY TO USE EXIT DOOR
ROOM 11, 13 AND 16 - DOUBLE KEY LOCKS, DEADBOLT REQUIRED.
- Open
CN140016 — DWELLING CLEAN AND SANITARY
MOST ROOMS, INCLUDING # 3, 1ST AND 2ND FLOOR BATHROOMS - MILDEW BUILD-UP.
- Open
PL157047 — STOP LEAKING WATER
ROOM # 3 - WATER LEAKING THROUGH THE CEILING.
- Open
CN110105 — LIGHT AND VENT
ROOM # 3 - WINDOW - MISSING.
- Open
CN104075 — WINDOW REPAIR FOR AIR SEEPAGE
MOST ROOMS, INCLUDING # 9 - WINDOWS DRAFTY, WITH AIR SEEPAGE.
- Open
CN107035 — MAINTAIN EXIT SIGN ILLUMINATED
1ST AND 2ND FLOOR - EXIT SIGNS - OUT OF SERVICE.
- Rodent-related
CN136016 — ROACHES
MOST ROOMS, INCLUDING # 3, 11 AND 12 - ROACHES INFESTATION.
- Open
CN136026 — INSECTS
MOST ROOMS, INCLUDING # 3, 11, 12 AND 13 - BEDBUGS INFESTATION THRU-OUT. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION.
- Open
CN198019 — FILE BLDG REGISTRATION
BLDG. - NOT REGISTERED FOR 2014
- Open
CN132046 — SAFE WORKING CONDITIONS
ROOM 11 - HEATING SOURCE - MISSING.
- Open
CN101025 — INT WALL/CEILING CHIP PLASTER
1ST FLOOR BATHROOM AND FRONT INTERIOR STAIRWELL - WALLS AND CEILINGS - BROKEN PLASTER.
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
2ND FLOOR BATHROOM AND ROOM # 3 - CEILINGS CAVING IN, WITH SEVERE WATER DAMAGE ON WALLS AND CEILINGS.
- Open
CN031013 — FIRE EXTNGSHR REQ, RESDNTL
2ND FLOOR HALLWAY - FIRE EXTINGUISHER - MISSING.
- Open
CN138056 — DEBRIS, EXCESSIVE
REAR ENCLOSED PORCH AND BASEMENT STAIRWAY - ACCUMULATION OF JUNK AND DEBRIS.
- Open
CN138026 — USE SANITARY REFUSE CONTAINERS
REAR BASEMENT STAIRWAY - ACCUMULATION OF REFUSE AND GARBAGE.
- Open
CN015062 — OBSTRUCTIONS IN EXIT WAY
REAR ENCLOSED PORCH AND BASEMENT STAIRWAY - JUNK AND DEBRIS OBSTRUCTING EGRESS.
- Open
CN070034 — REPLACE D&H PORCH
REAR METAL / WOOD PORCH IS IN DANGEROUS AND HAZARDOUS CONDITION - STRUCTURE IS UNSTABLE AND SWAYING, WITH STEEL FLOOR JOISTS RUSTING AND RAILING SECTIONS MISSING PICKETS. PLANS AND PERMIT REQUIRED TO REPLACE REAR PORCH.
- Open
CN103015 — REPAIR FLOOR
1ST AND 2ND FLOOR HALLWAY, INCLUDING BATHROOMS - FLOOR BOARDS BROKEN, WITH LOOSE, BROKEN AND BUCKLING TILES.
- Open
CN190019 — ARRANGE PREMISE INSPECTION
BUILDING INTERIOR - NO RESPONSE - UNVERIFIED DETECTORS AND CONDITIONS. UNABLE TO INSPECT INTERIOR STAIRWAYS.
- Open
CN061014 — REPAIR EXTERIOR WALL
SOUTH AT 2ND - LOOSE SIDING WITH PEELING PAINT.
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
2ND FLOOR BATH DAMAGED CEILING
- Open
CN031013 — FIRE EXTNGSHR REQ, RESDNTL
- Open
CN015062 — OBSTRUCTIONS IN EXIT WAY
REMOVE OBSTRUCTION DEBRIS FROM REAR PORCH EXIT
- Open
CN070034 — REPLACE D&H PORCH
REAR PORCH STRUCTURE UNSTABLE, FLOOR BOUNCES UNDER PRESSURE-RUSTED STEEL FLOOR JOIST SUPPORTS, ROOMING UNIT/BEDROOM BUILT OUT AT PORCH-ROOM 16 DANGEROUS AND HAZARDOUS REAR PORCH WOOD STAIRS MISSING BALLUSTERS
- Open
CN103015 — REPAIR FLOOR
2ND FLOOR, HALLWAY FLOORING SYSTEM IS DEFLECTING, BUCKLED
- Open
CN103025 — SUBMIT STRUCT. ENG. RPT (INT.)
PROVIDE ENGINEERS REPORT FOR BUT NOT LIMITED (1) 2ND FLOOR HALLWAY FLOOR SYSTEM
- Open
CN165017 — FLOOR, KIT & BATH NON-ABSORB
2ND FLOOR BATHROOM-ROTTED FLOORING
- Open
CN104035 — MAINTAIN WINDOW
ROOM 11 AND 13 UNFINISHED WINDOW REPAIRS,EXPOSED TO WEATHER
- Heat-related
CN132026 — HEAT HABITABLE ROOM
ROOM 11- NO HEAT SOURCE
- Open
CN015012 — NO KEY TO USE EXIT DOOR
ROOM 11 AND 13,16 DOUBLE KEY LOCK PROVIDE THUMBLATCH DEADBOLT NEW DRYWALL PARTITIONS 1ST AND 2ND FLOOR
- Open
NC2011 — PLANS & PERMITS REQ - CONTRCTR
PROVIDE PLANS AND PERMITS FOR CHANGE OF USE FROM COMMERCIAL AND 1 APARTMENT INTO S.R.O (2) INTERIOR ALTERATIONS TO 1ST AND 2ND FLOOR
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
PROVIDE SMOKE ALARM TO ROOM 16
- Open
CN194029 — PROVIDE
FIRST AND SECOND FLOORS EXIT DOORS ARE (32" WIDTH) UNDERSIZED PROVIDE 36" MINIMUM DOOR PER 13-160-220)
- Open
CN101025 — INT WALL/CEILING CHIP PLASTER
FRONT STAIRWELL HALL, 2N FLOOR HALLWAY, BROKEN PLASTER AT WALLS
About these City violation records
From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”
311 complaints (24 months)
No matching 311 complaints in the last 24 months.
Timeline
- Open City violation record — CN103015 REPAIR FLOOR
- Open City violation record — CN070034 REPLACE D&H PORCH
- Open City violation record — CN015062 OBSTRUCTIONS IN EXIT WAY
- Open City violation record — CN138026 USE SANITARY REFUSE CONTAINERS
- Open City violation record — CN138056 DEBRIS, EXCESSIVE
- Open City violation record — CN031013 FIRE EXTNGSHR REQ, RESDNTL
- Open City violation record — CN101015 REPAIR INTERIOR WALLS/CEILING
- Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
- Open City violation record — CN132046 SAFE WORKING CONDITIONS
- Open City violation record — CN198019 FILE BLDG REGISTRATION
- Open City violation record — CN136026 INSECTS
- Open City violation record — CN136016 ROACHES
- Open City violation record — CN107035 MAINTAIN EXIT SIGN ILLUMINATED
- Open City violation record — CN104075 WINDOW REPAIR FOR AIR SEEPAGE
- Open City violation record — CN110105 LIGHT AND VENT
- Open City violation record — PL157047 STOP LEAKING WATER
- Open City violation record — CN140016 DWELLING CLEAN AND SANITARY
- Open City violation record — CN015012 NO KEY TO USE EXIT DOOR
- Open City violation record — CN194029 PROVIDE
- Open City violation record — CN197019 INSTALL SMOKE DETECTORS
- Open City violation record — NC2011 PLANS & PERMITS REQ - CONTRCTR
- Open City violation record — NC2071 WORK NOT ALLOWED
- Open City violation record — CN104035 MAINTAIN WINDOW
- Open City violation record — CN103025 SUBMIT STRUCT. ENG. RPT (INT.)
- Open City violation record — CN103035 STRUCTURAL MEMBER, PIER BLOCK
- Open City violation record — CN066014 REPAIR ORIEL WINDOW
- Open City violation record — CN061014 REPAIR EXTERIOR WALL
- Open City violation record — CN190019 ARRANGE PREMISE INSPECTION
- Open City violation record — CN101025 INT WALL/CEILING CHIP PLASTER
- Open City violation record — CN194029 PROVIDE
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — NC2011 PLANS & PERMITS REQ - CONTRCTR
- Open City violation record — CN015012 NO KEY TO USE EXIT DOOR
- Open heat-related City violation record — CN132026 HEAT HABITABLE ROOM
- Open City violation record — CN104035 MAINTAIN WINDOW
- Open City violation record — CN165017 FLOOR, KIT & BATH NON-ABSORB
- Open City violation record — CN103025 SUBMIT STRUCT. ENG. RPT (INT.)
- Open City violation record — CN103015 REPAIR FLOOR
- Open City violation record — CN070034 REPLACE D&H PORCH
- Open City violation record — CN015062 OBSTRUCTIONS IN EXIT WAY
Recently closed / other violations (sample)
No recent closed violations in the sample.
Around 1606 W Grand Ave
- West Town community area: search another address
- No heat in your Chicago apartment? The heat ordinance and what to do
Nearby buildings with open City violation records
Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.
How the winter score is calculated
- Start at 100 (better = higher).
- Minus up to 40 for open heat/boiler-related building violations (12 pts each).
- Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
- Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
- Minus up to 15 for recent 311 building complaints (2 pts each).
- Extra −10 if 3+ open heat-related violations.
- Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
- Public records only — not an inspection, appraisal, or legal advice.
Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 12:22 PM CT.
ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.
“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.