All open City violation records (71)
No open City violation records dated in the last 24 months (since November 2024). The newest open one is from October 4, 2023. All 71 are collapsed below — still open, still counted.
Show 71 older open City violation records (before November 2024)
- Open
CN061014 — REPAIR EXTERIOR WALL
NORTH, EAST AND WEST ELEVATIONS - FRACTURES, LOOSE OR ERODED BRICKS/MORTAR AT VARIOUS LOCATIONS . ;SOUTH ELEVATION - FRACTURED, SPALLED , SHIFTED AND LOOSE TERRA COTTA FACADE . DANGEROUS AND HAZARDOUS. PROVIDE PROTECTIVE CANOPY AT FRONT MAIN ENTRANCE PRIOR AND DURING REPAIRS.
- Open
CN061074 — PROTECT SIDEWALK DURING CONST
SOUTH PUBLIC WALK INCLUDING PARTIAL EAST NEIGHBORING SECTION - IMMEDIATELY PROVIDE EMERGENCY SCAFFOLDING OR PROTECTIVE CANOPY OVER THE PUBLIC WAY FOR THE PROTECTION OF PEDESTRIANS FROM UNSAFE BUILDING CONDITIONS AND PREVENT IMMINENT HARM TO PEOPLE OR PROPERTY. A BUILDING PERMIT APPLICATION COVERING THE SCOPE OF THE EMERGENCY REPAIR MUST BE SUBMITTED TO THE DEPARTMENT OF BUILDINGS ON THE NEXT BUSINESS DAY. A PERMIT APPLICATION FOR THE SCAFFOLDING/CANOPY MUST BE SUBMITTED TO THE DEPARTMENT OF BUILDINGS WITHIN 3 BUSINESS DAYS OF ERECTION. THE DEPARTMENT OF TRANSPORTATION MAY NOT ISSUE A PERMIT FOR USE OF THE PUBLIC WAY TO INSTALL SCAFFOLDING/CANOPY UNLESS A PERMIT FOR THE SCAFFOLDING/CANOPY HAS BEEN OBTAINED FROM THE BUILDING DEPARTMENT. (14A-4-401.1.1, 14A-4-401.1.2, 14A-4-404.16 THROUGH 14A-4-404.16.5, 14A-4-404.22.3 AND 14B-33-3306)
- Open
CN061024 — SUBMIT 2 COPY STRUCTURAL RPT
PROVIDE CONDITIONS ASSESMENT REPORT OF ALL ELEVATIONS INCLUDING SOUTH ELEVATION TERRA COTTA AND NORTH LIGHTING STRUCK AREA PER SECTIONS (14X-1-1-4.1, 14X-1-104.2, 14X.1.104.3, 14X-1-104.4, 14A-4-411.1, 14A-4-412.1.1, 14A-6-603.5)PLANS AND PERMITS ARE REQUIRED PER REPORT FOR REPAIRS/REBUILD . ALL WORK IS SUBJECT TO FIELD INSPECTION AND APPROVAL (SEC 14A-4-401.1
- Open
CN194029 — PROVIDE
SUBMIT CONDITION ASSESSMENT REPORT. REPORT SHALL BE SIGNED AND SEALED BY A REGISTERED DESIGN PROFESSIONAL, AND BASED ON A CRITICAL, COMPREHENSIVE, AND DETAILED PHYSICAL INSPECTION OF THE PREMISES IDENTIFIED AND DETAILED IN THE VIOLATION. THE CONDITION REPORT MUST IDENTIFY THE DATE, NATURE, SCOPE, FINDINGS, AND DEFICIENCIES OF THE INSPECTION/INVESTIGATION. THE REPORT MUST IDENTIFY EACH TECHNICAL PRINCIPLE OR STANDARD THAT IS THE BASIS OF ANY PROFESSIONAL JUDGMENT AND COMPREHENSIVE RECOMMENDATIONS FOR REPAIRS EXPRESSED IN THE REPORT. RECOMMENDATION OF REPAIRS MUST INCLUDE PHOTOS, DRAWINGS, DETAILS, AND CALCULATIONS WHICH CAN BE SUBMITTED FOR A REPAIR PERMIT IF NECESSARY. THE CONDITION REPORT, PERMIT, AND CONSTRUCTION DOCUMENTS MUST BE KEPT ON FILE AT THE PREMISES AND MADE AVAILABLE FOR FIELD INSPECTION REVIEW AND APPROVAL BY ALL RELATED TRADES. SUBMIT ELECTRONIC REPORT FOR REVIEW AND APPROVAL TO: DOB_CAR@CITYOFCHICAGO.ORG (14X-1-104.1 THRU 14X-1-104.4, 14A-6-603.5, AND 14A-4-411.1)PROVIDE SIGNED LETTER FROM LICENSED MASON STATING THE SCOPE OF WORK COMPLETED AND ATTESTING TO THE FACT THAT NO MORE LOOSE OR POTENTIALLY DANGEROUS MATERIAL EXISTS AT THE NORTHEAST CORNER SPECIFICALLY.
- Open
CN061014 — REPAIR EXTERIOR WALL
NORTH ELEVATION /EXTERIOR WALL - LOOSE, SHIFTED AND FALLEN BRICK SECTIONS WITH WASHED OUT MORTAR JOINTS. EAST ELEVATION /EXTERIOR WALL - MASONRY FRACTURES WITH WASHED OUT MORTAR JOINTS. SOUTH ELEVATION /EXTERIOR WALL - CRACKED TERRA COTTA SECTIONS.
- Open
CN062034 — REPAIR COPING
NORTHEAST CORNER /COPING TILES - CRACKED, BROKEN AND FALLEN COPING SECTIONS.
- Open
NC5042 — SELF-CLOSE CLASS B FIRE DOOR
2ND FLOOR SOUTH INTERIOR STAIR - STAIRWELL DOOR MISSING CLOSER.
- Open
CN140016 — DWELLING CLEAN AND SANITARY
2ND FLOOR DWELLING UNIT 204 - GARBAGE, JUNK AND DEBRIS ON KITCHEN AND LIVING ROOM FLOOR. FILTHY AND UNSANITARY CONDITIONS.
- Open
CN141016 — STOP SMOKE, NOXIOUS ODORS
2ND FLOOR DWELLING UNIT 204 - SMOKE AND NOXIOUS ODORS IN ENTIRE DWELLING UNIT. STRONG SMELL OF GARGAGE AND ROTTING FOOD.
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
MAKE NECESSARY REPAIUS TO GOVERNOR AND SOFEFLOS - SCHEDULE
- Open
EV1110 — MAINTAIN OR REPAIR ELECT ELEVA
FIRE SERVICE TO BE TESTED IN ITS ENTIRETY PRIOR TO FINAL
- Open
NC3042 — UNINTERRUPTED EXIT AT GRADE
REMOVE OBSTRUCTION FROM FIRE SCAPES
- Open
IR0000 — SEND EX. METAL LETTER
ENG REPORT
- Open
IR0055 — PROTECT METAL MEMBERS
SCRAPE & PAINT
- Open
CN136026 — INSECTS
UNIT 805, 1204, 509 BED BUG INFESTATION. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION.
- Open
CN197019 — INSTALL SMOKE DETECTORS
NO SMOKE DETECTOR TOP OF SOUTH STAIR.
- Open
CN105015 — REPAIR DOOR, INT.
STAIRWELL DOOR AT 10 NORTH, 11 NORTH, 11 SOUTH, 12 NORTH, NOT CLOSING PROPERLY, HITTING FRAMES, RUBBING.
- Open
CN063014 — CHIMNEY
CHIMNEY ON EAST SIDE OF BUILDING- DUCT EXTENDING FROM BUILDING INTO CHIMNEY- RUSTED, HOLES.
- Open
CN031023 — FIRE EXTNGSHR RECHARGE & TAG
FIRE EXTINGUISHERS WITH EXPIRED TAGS THROUGHOUT BUILDING.
- Open
CN136026 — INSECTS
UNIT 805, 1204, 509 BED BUG INFESTATION. PROPERTY MUST BE EFFECTIVELY TREATED TO EXTERMINATE BED BUGS THROUGHOUT, BY EMPLOYING AN EXPERIENCED EXTERMINATOR IN ABATEMENT OF BED BUG INFESTATION. BUILDING DEPARTMENT WILL NOT CONSIDER THIS VIOLATION COMPLIED WITHOUT PROOF OF SAID EXTERMINATION.
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
NORTH STAIRWELL FROM 10TH FLOOR TO 12TH- WATER DAMAGED, FALKING PAINT AND PLASTER. SOUTH STAIRWELL FROM 12 TO ROOF WATER DAMAGE, FLAKING PAINT AND PLASTER.
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
SMOKE DETECTOR NOT OPERATING UNIT 505.
- Open
CN061014 — REPAIR EXTERIOR WALL
EAST ONE STORY BUILDING SECTION AT SOUTH ELEVATION, SIDING TORN ,LOOSE AND MISSING.
- Open
CN063034 — CHIMNEY HEIGHT
WEST AT GRADE AT CENTER- METAL CHIMNEY STACK STICKING THROUGH WINDOW PANEL AND STOPS AND SECOND FLOOR. PERMIT REQUIRED TO INSTALL CHIMNEY FLUE PIPE.
- Open
CN063014 — CHIMNEY
EAST LARGE METAL CHIMNEY FROM GRADE TO ROOF- RUSTED WITH FLAKING ,WORN FINISH.
- Open
CN197079 — REPAIR/REPLACE SMOKE DETECTORS
APARTMENT 410- SMOKE DETECTOR MISSING FROM CEILING MOUNT PLATE.
- Open
CN197019 — INSTALL SMOKE DETECTORS
APARTMENT 912- MISSING SMOKE DETECTER.
- Heat-related
CN132016 — HEAT UNIT ADEQUATELY
APARTMENT 406-HEATING SYSTEM IS ON AT TIME OF INSPECTION, HEAT IS INSUFFICIENT. ROOM TEMPERATURE 65F.
- Open
CN104075 — WINDOW REPAIR FOR AIR SEEPAGE
APARTMENT 306- WINDOWS GAPS AND CRACKS IN LIVING ROOM AND BEDROOM , DRAFTY WINDOWS, COLD AIR SEEPAGE, STAINED WALL BELOW WINDOWS FROM WATER AND MOISTURE LEAKS.
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE MECHANICAL PROTECTION FOR ELEVATOR CAB LIGHTING. (A17.1 1996 RULE 204.7(D). SERVICE CAR.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR FIREMAN'S SERVICE: 1) AUDIBLE SIGNAL SHALL GO OFF WHEN CAR ARRIVES IN LOBBY. 2) AUDIBLE SIGNAL SHALL GO OFF WHEN CAR ARRIVES IN LOBBY. 2) DOOR DETECTOR MUST BE DISABLED ON PHASE II. 18-30-010, 13-20-120. EV005385.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR FIREMANS SERVICE: 1) KEYS SHOULD NOT BE REMOVABLE ON PHASE ! OR PHASE II. REAR PASSENGER.
- Open
199029 — OPEN TYPE VIOLATION
LABEL LANDING DOORS ON CAR SIDE WITH FLOOR NUMBER. SERVICE CAR.
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE WORKING ALARMBELL (A17.1-1996 RULE 211.1). SERVICE ELEVATOR.
- Open
199029 — OPEN TYPE VIOLATION
INSTALL DOOR LOCK COVERS WHERE MISSING. FRONT AND REAR ELEVATORS.
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE ADEQUATE MACHINE ROOM LIGHTING WITH BULB GUARDS (A17.1A-1997) RULE 204.7A (3). FRONT, REAR AND SERVICE ELEVATORS.
- Open
199029 — OPEN TYPE VIOLATION
CLEAN ELEVATOR MACHINE ROOM, CARTOP AND PIT (A17.1-1996 RULE 1206) FRONT, REAR AND PASSENGER ELEVATORS.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR DOOR RESTRICTOR (A17.1A-1997 RULE 111.5) FRONT & REAR PASSENGER.
- Open
199029 — OPEN TYPE VIOLATION
FREIGHT CAR. ENCLOSE CAB LIGHTING. (18-30-010 & 13-20-120) EV005385
- Open
199029 — OPEN TYPE VIOLATION
REAR CAR. REPAIR DOOR RESTRICTOR TO OPERATE PROPERLY.
- Open
199029 — OPEN TYPE VIOLATION
FREIGHT CAR. REPAIR ALARM BELL TO OPERATE PROPERLY.
- Open
CN136026 — INSECTS
BED BUG INFESTATION-THROUGHOUT THE PREMISES.PROPERTY NEEDS EXTERMINATION BY A CERTIFIED BED BUG EXTERMINATOR THROUGHOUT THE PREMISES.BUILDING DEPT.WILL NOT CONDSIDER THIS ITEM COMPLIED WITHOUT PROOF OF SAID EXTERMINATION AND PROOF OF EXERMINATOR'S QUALIFICATION SPECIFICALLY WITH REGARD TO BED BUG
- Open
CN136026 — INSECTS
BED BUG INFESTATION-THROUGHOUT THE PREMISES.PROPERTY NEEDS EXTERMINATION BY A CERTIFIED BED BUG EXTERMINATOR THROUGHOUT THE PREMISES.BUILDING DEPT.WILL NOT CONDSIDER THIS ITEM COMPLIED WITHOUT PROOF OF SAID EXTERMINATION AND PROOF OF EXERMINATOR'S QUALIFICATION SPECIFICALLY WITH REGARD TO BED BUG
- Open
CN073054 — REPAIR EXTERIOR DOOR, RESET
RESET ALL DOORS AT STAIRWELL
- Open
IR0000 — SEND EX. METAL LETTER
EXPOSED METAL LETTER
- Open
IR0055 — PROTECT METAL MEMBERS
PROTECT METAL MEMBERS
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE WORKING CARTOP LIGHT (A17.1A-1997 RULE 204.7A (4). FRONT ELEVATOR.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR/REPLACE DEFECTIVE 1ST FLOOR SIGHT GUARD A17.1A-97 RULE 110.11J. REAR ELEVATOR.
- Open
199029 — OPEN TYPE VIOLATION
INSTALL DOOR LOCK COVERS WHERE MISSING. FRONT AND REAR ELEVATORS.
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE ADEQUATE MACHINE ROOM LIGHTING WITH BULB GUARDS (A17.1A-1997) RULE 204.7A (3). FRONT, REAR AND SERVICE ELEVATORS.
- Open
199029 — OPEN TYPE VIOLATION
CLEAN ELEVATOR MACHINE ROOM, CARTOP AND PIT (A17.1-1996 RULE 1206) FRONT, REAR AND PASSENGER ELEVATORS.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR DOOR RESTRICTOR (A17.1A-1997 RULE 111.5) FRONT & REAR PASSENGER.
- Open
199029 — OPEN TYPE VIOLATION
FREIGHT CAR. REPAIR ALARM BELL TO OPERATE PROPERLY.
- Open
199029 — OPEN TYPE VIOLATION
FRONT CAR. REPAIR DOOR RESTRICTOR TO OPERATE PROPERLY.
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE MECHANICAL PROTECTION FOR ELEVATOR CAB LIGHTING. (A17.1 1996 RULE 204.7(D). SERVICE CAR.
- Open
199029 — OPEN TYPE VIOLATION
FREIGHT CAR. ENCLOSE CAB LIGHTING. (18-30-010 & 13-20-120) EV005385
- Open
199029 — OPEN TYPE VIOLATION
FREIGHT CAR. REPAIR CAR SWITCH TO RETURN TO CENTER (OFF POSITION) WHEN RELEASED.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR FIREMAN'S SERVICE: 1) AUDIBLE SIGNAL SHALL GO OFF WHEN CAR ARRIVES IN LOBBY. 2) AUDIBLE SIGNAL SHALL GO OFF WHEN CAR ARRIVES IN LOBBY. 2) DOOR DETECTOR MUST BE DISABLED ON PHASE II. 18-30-010, 13-20-120. EV005385.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR FIREMANS SERVICE: 1) KEYS SHOULD NOT BE REMOVABLE ON PHASE ! OR PHASE II. REAR PASSENGER.
- Open
199029 — OPEN TYPE VIOLATION
REPAIR/ADJUST CAR SWITCH TO RETURN TO CENTER POSITION. SERVICE ELEVATOR.
- Open
199029 — OPEN TYPE VIOLATION
LABEL LANDING DOORS ON CAR SIDE WITH FLOOR NUMBER. SERVICE CAR.
- Open
199029 — OPEN TYPE VIOLATION
PROVIDE WORKING ALARMBELL (A17.1-1996 RULE 211.1). SERVICE ELEVATOR.
- Open
199029 — OPEN TYPE VIOLATION
REAR CAR. REPAIR DOOR RESTRICTOR TO OPERATE PROPERLY.
- Rodent-related
CN136016 — ROACHES
#609 ROACHES OBSERVED
- Open
PL154027 — SUPPLY HOT WTR MIN TEMP 120DEG
#609 HOT WATER TEMPERATURE IN KITCHEN & BATHROOM 95
- Open
CN197019 — INSTALL SMOKE DETECTORS
#609 NO SMOKE ALARM
- Open
CN101015 — REPAIR INTERIOR WALLS/CEILING
#609 CEILING THRU OUT UNIT SPALLING & LOOSE SECTIONS PLASTER & PAINT.
- Open
CN073014 — REPAIR EXTERIOR DOOR
REHANG REAR STAIRWELL DOOR 4-3-6TH FL FIRE ESCAPE
- Open
CN105015 — REPAIR DOOR, INT.
INTERIOR STAIRWELL DOOR KNOB 9-8-2
- Open
CN190019 — ARRANGE PREMISE INSPECTION
NO ENTRY TO APTS
- Open
CN107015 — ILLUMINATE PUBLIC STAIR/HALL
INTERIOR EXIT ELLUMINATIONS REAR STAIRWELL &CORIDOOR,11 COORDOOR, 8TH FL REAR STAIRWELL, 2ND FL REAR STAIRWELL
About these City violation records
From the City of Chicago Building Violations dataset description: “…informational only and does not necessarily reflect the current condition of the building or property. The dataset contains cases where a respondent has been found to be liable as well as cases where the respondent has been found to be not liable.”
311 complaints (24 months)
- building
Building Violation
- building
Building Violation
- building
Building Violation
Timeline
- 311 building — Building Violation
- 311 building — Building Violation
- 311 building — Building Violation
- Open City violation record — CN061024 SUBMIT 2 COPY STRUCTURAL RPT
- Open City violation record — CN061074 PROTECT SIDEWALK DURING CONST
- Open City violation record — CN061014 REPAIR EXTERIOR WALL
- Open City violation record — CN062034 REPAIR COPING
- Open City violation record — CN061014 REPAIR EXTERIOR WALL
- Open City violation record — CN194029 PROVIDE
- Open City violation record — CN141016 STOP SMOKE, NOXIOUS ODORS
- Open City violation record — CN140016 DWELLING CLEAN AND SANITARY
- Open City violation record — NC5042 SELF-CLOSE CLASS B FIRE DOOR
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Open City violation record — IR0055 PROTECT METAL MEMBERS
- Open City violation record — IR0000 SEND EX. METAL LETTER
- Open City violation record — NC3042 UNINTERRUPTED EXIT AT GRADE
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — CN101015 REPAIR INTERIOR WALLS/CEILING
- Open City violation record — CN136026 INSECTS
- Open City violation record — CN031023 FIRE EXTNGSHR RECHARGE & TAG
- Open City violation record — CN063014 CHIMNEY
- Open City violation record — CN105015 REPAIR DOOR, INT.
- Open City violation record — CN197019 INSTALL SMOKE DETECTORS
- Open City violation record — CN136026 INSECTS
- Open City violation record — CN104075 WINDOW REPAIR FOR AIR SEEPAGE
- Open heat-related City violation record — CN132016 HEAT UNIT ADEQUATELY
- Open City violation record — CN197019 INSTALL SMOKE DETECTORS
- Open City violation record — CN197079 REPAIR/REPLACE SMOKE DETECTORS
- Open City violation record — CN063014 CHIMNEY
- Open City violation record — CN063034 CHIMNEY HEIGHT
- Open City violation record — CN061014 REPAIR EXTERIOR WALL
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
- Open City violation record — 199029 OPEN TYPE VIOLATION
Recently closed / other violations (sample)
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
CN061014 REPAIR EXTERIOR WALL
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
- Closed / other
EV1110 MAINTAIN OR REPAIR ELECT ELEVA
Around 1246 W Pratt Blvd
- Rogers Park building violations and 311 complaints
- Loyola Chicago off-campus housing: Rogers Park renter guide
- No heat in your Chicago apartment? The heat ordinance and what to do
Nearby buildings with open City violation records
Nearby addresses that also have open City violation records in the City of Chicago Building Violations dataset (22u3-xenr), by distance. Open each one for its current free report.
How the winter score is calculated
- Start at 100 (better = higher).
- Minus up to 40 for open heat/boiler-related building violations (12 pts each).
- Minus up to 45 for other open building violations (2 pts each, plus extras above 20 and 100 open).
- Minus up to 20 for rodent-related open violations and 311 rodent complaints (4 pts each).
- Minus up to 15 for recent 311 building complaints (2 pts each).
- Extra −10 if 3+ open heat-related violations.
- Chicago 311 takes no-heat complaints, but the City's public 311 dataset does not publish them as a separate type, so heat here comes from open Department of Buildings heat-related violations (codes/descriptions, e.g. CN132016 HEAT UNIT ADEQUATELY). 311 building complaints are counted separately, not as heat.
- Public records only — not an inspection, appraisal, or legal advice.
Sources: City of Chicago Building Violations (data.cityofchicago.org/d/22u3-xenr); City of Chicago 311 Service Requests (data.cityofchicago.org/d/v6vf-nfxy). Data: City of Chicago (chicago.gov). Data as of November 21, 2026 at 9:01 AM CT.
ScoutMyBuilding summarizes publicly available City data. It is informational only — not legal advice, not a housing inspection, and not a guarantee of current building conditions. City records may be incomplete, delayed, or inaccurate. Always verify with the City of Chicago Department of Buildings, 311, and your own walkthrough before signing a lease.
“This site provides applications using data that has been modified for use from its original source, www.cityofchicago.org, the official website of the City of Chicago. The City of Chicago makes no claims as to the content, accuracy, timeliness, or completeness of any of the data provided at this site. The data provided at this site is subject to change at any time. It is understood that the data provided at this site is being used at one’s own risk.” Required by the City of Chicago Data Terms of Use.